background image

Door Monitor Alarm (DMA)

rev. 09/02/21

47290_ins_BAPI_DMA

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

 Installation & Operations

3 of 4

Termination

Operation

All terminal blocks are removable and 

pluggable connectors.
16 to 22 AWG wire is required for all 

connections.

POWER:

 

24 VAC or 24 VDC

(UL Listed Class 2 Power Source only)

DOOR SWITCH:

 

Connect the switch’s wires. No 

polarity.

AUXILIARY RELAYS:

 

Can be connected as either Normally 

Open (NO) or Normally Closed (NC).

AUDIBLE ANNUNCIATOR:

 

Remove the cover sticker prior to use.

Fig. 3:

 DMA Circuit Board

When the door opens, the Door Switch creates a closed circuit. The Door Status LEDs on the 

face of the unit change color, both Auxiliary Relays energize (providing dry contact outputs), 

and both Auxiliary Relay LEDs illuminate. If the door stays open longer than the Door Timer 

Interval setting, the audible annunciator sounds (See Chart below).
Closing the door de-energizes both of the Auxiliary Relays, silences the audible annunciator 

if it is on, and changes the color of the Door Status LEDs. The Auxiliary Relays are energized 

whenever the door is open and de-energized whenever it is closed.

Door Status

Additional Condition

User Action

Green

Solid

Closed

N/A

None.

Amber Flashing

Open

Door timer interval has not been exceeded.

Close the door when completed with your work.

Amber

Solid

Closed

5 minute Audible Annunciator Reset Interval has 

not expired.

Avoid opening the door until the LEDs turn green.

Red

Flashing

Open

Door timer interval exceeded.

Close the door as soon as possible.

Color

Door Status LEDs 

(located on the face of the unit)

Door Timer Interval Switch:

The user can select how long the door can be continuously open before the audible 

annunciator sounds and the status LEDs turn red. Figure 4 shows the allowable settings. 

If the switch is in one of the blank positions, it uses 1 min.

Fig. 4:

 Door Timer Interval 

Rotary Switch (S1)

Auxiliary Relay 

Connections

Power 

Connection

Power 

On LED 

(green)

Relay LEDs 

(red)

Door Switch Connection

Remove Sticker 

Prior to Use!

BAPI recommends using twisted pair of at least 22AWG for all wire connections. Larger gauge wire may be required for 

long runs. All wiring must comply with the National Electric Code (NEC) and local codes. 
Do NOT run this device’s wiring in the same conduit as AC power wiring of NEC class 1, NEC class 2, NEC class 3 or with 

wiring used to supply highly inductive loads such as motors, contactors and relays. BAPI’s tests show that fluctuating and 

inaccurate signal levels are possible when AC power wiring is present in the same conduit as the signal lines. If you are 

experiencing any of these difficulties, please contact your BAPI representative.

BAPI recommends wiring the product with power disconnected. Proper supply voltage, polarity and wiring 

connections are important to a successful installation.  Not observing these recommendations may damage the 

product and void the warranty.

Отзывы: