Product Identification and Overview

Specifications

Fig. 2:

 DMA Mounting Diagram

The BAPI Door Monitor Alarm (DMA) monitors a door switch to 

alert personnel when the door is closed, open or has exceeded its 

user-selectable open time period. Green, amber and red LEDs on 

the face of the unit alert nearby personnel the door’s status. 
Leaving the door open for longer than the user-selected time 

will also energize an internal audible annunciator to alert nearby 

personnel that the door should be closed immediately. The unit 

also contains two auxiliary relays that will energize whenever the 

door is opened to alert other user-supplied warning devices or a 

building automation system.
A green LED inside the unit illuminates whenever power 

is present and red LEDs inside the illuminate when the 

auxiliary relays are energized to assist with installation and 

troubleshooting.

Mounting

Fig. 1:

 

DMA Unit

1.  Mount the unit on a solid, non-vibrating 

surface. The orientation doesn’t matter.

2.  Use the mounting template on the next 

page (or the enclosure itself) to to mark 

the pilot-hole locations. Use the 4 included 

#10 (M5) screws on the four mounting 

feet of the enclosure. A pilot-hole makes 

mounting easier.

3.  Place the provided #6 screws into the 

holes on each side of the lid latch to make 

the cover tamper resistant.

Power: 

24 VAC or 24 VDC (UL Listed Class 2 Power Source only)

Power Consumption (max):

7.5 VA @ 24 VAC, 200 mA @ 24 VDC

Door Switch Contacts:

 

Normally Closed (NC) = door open is alarm condition

Normally Open (NO) = door closed is alarm condition

Auxiliary Relay Contact Rating:

 

1.0 Amp @ 30 VAC/VDC

Audible Annunciator: 

90dB; 2,730 Hz

Wiring:

 16 to 22 AWG

Environmental Operation Range:

Temp: 32 to 140 °F (0 to 60 °C)

Humidity: 5 to 95%, non-condensing

Enclosure Material: 

UV-resistant Polycarbonate, UL94, V-0

Enclosure Rating:

 

IP66, NEMA 4

Agency: 

CE EN 61326-1:2013 EMC (Industrial 

Electromagnetic Environment), UL94 V-0, RoHS

Specifications subject to change without notice.