BAPI BAPI-Stat Quantum Slim Скачать руководство пользователя страница 4

BAPI-Stat “Quantum Slim” Wireless Room 

Temperature Transmitter

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

Specifications subject to change without notice.

4 of 4

 Installation & Operations

39907_ins_wireless_QuantumSlim

rev. 02/07/18

FCC Wireless Certification and Interference Statement

Wireless BAPI-Stat “Quantum Slim” Room Transmitter (QSL900) - FCC ID: T4FQSL900

This equipment has been tested and found to comply with the limits for a class B digital device, pursuant to part 15 of 

the FCC Rules.  These limits are designed to provide reasonable protection against harmful interference in a residential 

installation.  This equipment generates, uses, and can radiate radio frequency energy, and if not installed and used in ac-

cordance with the instructions, may cause harmful interference to radio communications.  However, there is no guarantee 

that interference will not occur in a particular installation.  If this equipment does cause harmful interference to radio or 

television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct 

the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.

• Increase the separation between the equipment and receiver.

• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

• Consult the dealer or an experienced radio / TV technician for help.
In order to maintain compliance with FCC regulations, shielded cables must be used with this equipment.  Operation with 

non-approved equipment or unshielded cables is likely to result in interference to radio and TV reception.  The user is 

cautioned that changes and modifications made to the equipment without the approval of the manufacturer could void the 

user’s authority to operate this equipment.

Possible Problems:

Temperature value is not 

being received properly by 

the Gateway

Sensor is not 

communicating with the 

Gateway

Diagnostics

Possible Solutions:

Verify that the controller’s software is configured properly.
Make sure the transmitters are within range of the receiver/gateway.
Verify proper power and termination of the receiver/gateway as shown in the Gateway/

Receiver instructions document “39021_RCV_900_BACnet.pdf” available on the BAPI 

website or by contacting BAPI.
Check that the receiver/gateway’s yellow LED to the left of the Ethernet cable jack is 

illuminated and that the green LED to the right is blinking indicating a good Ethernet 

network connection and network activity.

Perform the “Wireless Sensor Reset” procedure as described above and in 

the Gateway 

instructions document “39021_RCV_900_BACnet.pdf” available on the BAPI website or 

by contacting BAPI.

 Wireless Sensor Reset

Pressing the “Ping/Training” button on a wireless sensor for 15 seconds will reset the sensor to the original factory 

default settings (which are accessed through the associated Gateway receiver). This reset procedure can be used to 

re-establish communication between the sensor and the Gateway if communication is lost due to mismatched 

addresses. The address of the sensor will be reset to the default: 42415049. This default address can then be entered 

for the Gateway (as described in the Gateway instructions document “39021_RCV_900_BACnet.pdf”) to re-establish 

communication with the sensor. Once communication is established, the address of the Gateway and the sensor can 

be returned to the previous address to re-establish communication with the other sensors on the network (as described 

in the Gateway instructions document “39021_RCV_900_BACnet.pdf”).
Besides reseting the wireless address, the reset procedure will also return the sensor to these default values: 
Channel = 1, 3 • Transmit power = 0 dBm • Reported intervals = 300 seconds • Sample Interval = 300 seconds 

• AES key = not affected by the reset procedure • Battery warning Voltage = 2.5 • All offsets = 0

Отзывы: