BAPI-Stat “Quantum Slim” Wireless Room
Temperature Transmitter
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
Specifications subject to change without notice.
2 of 4
Installation & Operations
39907_ins_wireless_QuantumSlim
rev. 02/07/18
Initial Activation
Fig. 6:
Cover
removed from
base plate on
battery power
unit
Fig. 7:
Battery
insulator tab
removal
1. Place the base plate against the wall where you want to mount the
sensor and mark the two mounting holes.
2. Drill two 3/16” holes in the center of each marked mounting hole. Insert
a drywall anchor into each hole.
3. Secure the base to the drywall anchors using the #6 x 1 inch mounting
screws provided.
4. Attach Cover by latching it to the top of the base, rotating the cover
down and snapping it into place. Secure the cover by backing out the
lock-down screws using a 1/16” Allen wrench until they are flush with the
bottom of the cover.
5. For units with an internal sensor the mounting process is complete.
6. For remote sensors, string the wire through the freezer door and place
the sensor in the best location to measure the required temperature.
7. Mount the External Probe using a Flexible Probe Bracket (Fig. 4) or use
the clip or screw hole on the Hanging Bracket Sensor (Fig. 5)
Fig. 3:
BAPI-Stat “Quantum Slim” Mounting
Drywall Mounting
Fig. 4:
External Probe Mounting with a
Flexible Probe Bracket (BA/FPB)
Fig. 5:
External
Hanging Bracket
Sensor Mounting
1.
Cover Removal:
Remove the cover from the base
plate by turning in the cover lockdown screw with
a 1/16” Allen wrench (as described in the Mounting
Section) until the cover can be removed (Fig 6).
2.
Battery Tab Insulator Removal for Battery Power
Units:
If the unit is ordered with battery power, it will
come with two pre-installed batteries. To activate
the unit, find the battery tab insulators and pull
them out (Fig. 7). The unit will begin transmitting at
approximately 5 minute intervals.
3.
Applying Power to Wired Units:
If the unit is
ordered with wired power, it will have a power
terminal block near the top center of the unit. To
activate the unit, apply 9 to 30 VDC (50 mA max)
or 15 to 28 VAC (50 mA max) (Fig. 9). The unit will
begin transmitting at approximately 5 minute intervals
after power is applied.
4.
Cover Replacement:
Attach Cover by latching it
to the top of the base, rotating the cover down and
snapping it into place. Secure the cover by backing
out the lock-down screws using a 1/16” Allen wrench
until they are flush with the bottom of the cover.
Fig. 9:
Power
applied to
terminal block
Fig. 8:
Cover
removed from
base plate on
battery power
unit