4xxxx Registers
Parameters
SP3
SP4
3641–3643
3661–3663
36x3 Hold Last Voltage Enable
36x1 Continuous Voltage Setting. Use this voltage parameter to set the output voltage when supplying continuous power through the
SP# terminals (not associated with inputs). The Continuous Voltage parameter cannot be used if any input uses switch power. To set a
continuous voltage on the SP output, also turn on the default output condition “default on power up.” This will turn on this continuous
voltage output when the radio powers up.
Output Voltage
Parameter Value
Output Voltage
Parameter Value
0V
255
15V
32
5V
204
20V
12
7V
125
24V
03
10V
69
36x2 Default Output State. The Default Output State parameter represents the default condition of the switch power output. When com-
munication is lost to the host or the wireless link is lost for the I/O data radio, the data radio can set the outputs and switch power outputs
in this default state. When set to 0, the switch power is turned off. When set to 1, the switch power is set to the voltage established by the
Continuous Voltage Setting.
36x3 Hold Last State Enable. Set Hold Last State Enable to 1 to set the switch power output to its last known value when communica-
tions are lost. Set this parameter to 0 to disable the Host Last State Enable and use the Default Output State settings.
43700s Discrete Output Parameters
The following characteristics are configurable for each of the discrete outputs. Parameters for Output 1 start at 43701 through 43703.
Parameters for Output 2 start at 43721 through 43723. Each following input is offset from the previous one by 20 registers.
4xxxx Registers
Parameters
Discrete Output
Parameters
Output 1
Output 2
Output 3
Output 4
3701–3703
3721–3723
3741–3743
3761–3763
3xx1 Default Output State
3xx2 Hold Last State Enable
3xx3 Enable Switch Power Logic
3xx1 Default Output State. The Default Output State parameter represents the default condition of the discrete output. When an error
condition exists, the outputs are set to this user-defined output state, either a 0 or a 1.
3xx2 Hold Last State Enable. Set the Hold Last State to 1 to set the output to its last known value before the error occurred. Set this
parameter to 0 to disable the Hold Last State and use the Default Output State setting during an error condition.
3xx3 Enable Switch Power Logic.
44000s Analog Output Parameters
The following characteristics are configurable for each of the analog outputs. Parameters for Analog Output 1 start at 44001 through
44005. Parameters for Analog Output 2 start at 44021 through 44025. Each following input is offset from the previous one by 20 regis-
ters.