TROUBLESHOOTING
In a Host-connected DX80 system, a link time-out will result in an error code (53 or 0x35xx) being placed in the Node-specific DEVICE
MESSAGE Modbus register (Node 1 = Register 24, Node 2 = Register 40, etc.).
In order for the RF link to be reinstated, the Host must send a control message to clear the device error message. Any Node output
registers will be re-populated by the latest Gateway register map.
RF Link Time-out & Recovery – Host-connected
Link between Gateway and Node 1 recovered.
It is the responsibility of the Host to handle Node device error messages. This will result in outputs being reinstated.
Link between Gateway and Node 1 timed out.
*