DXMR90-X1 Series Controller Instruction Manual

 

 

20

Continued from page 19

Local Registers 

Type 

Description 

7001–8000 

32-bit non-volatile integer 

Data flash, non-volatile 

> 10000 

 

Read-only virtual registers, system-level data 

Local Registers 1–845 and 5001–7000 (Internal Processor Memory, 32-bit, Unsigned)—The Local Registers are the main 

global pool of registers. Local Registers are used as basic storage registers and as the common data exchange mechanism. 

External Modbus device registers can be read into the Local Registers or written from the Local Registers. The 

DXMR90-X1, 

as a Modbus master device or a Modbus slave device, exchanges data using the Local Registers. Modbus over Ethernet 

(Modbus/TCP) uses the Local Registers as the accessible register data. 

Local Registers 846–849 (Reset, Unsigned)—These Local registers are reserved for use as Reset registers. A time interval 

can be specified in the configuration software for the DXM to reset. If the data in the register does not change within the user-

specified time interval, the DXM resets. 

Local Registers 851–900 and 7001–8000 (Data Flash, Non-volatile, 32-bit, Unsigned)—The top 50 Local Registers are spe-

cial non-volatile registers. The registers can store constants or calibration type data that must be maintained when power is 
turned off. This register data is stored in a data flash component that has a limited write capability of 100,000 cycles, so these 

registers should not be used as common memory registers that change frequently. 

Local Registers 1001–5000—These Local Registers are paired together to store a 32-bit IEEE floating point format number in 
big endian format. Registers 1001 [31:16], 1002 [15:0] store the first floating point value; registers 1003, 1004 store the sec-
ond floating point number. There are a total of 2000 floating point values; they are addressed as two 16-bit pieces to accom-

modate the Modbus protocol. Use these registers when reading/writing external devices that require Modbus registers in 
floating point format. Since Modbus transactions are 16-bits, the protocol requires two registers to form a 32-bit floating point 

number. 

Virtual Registers

—The 

DXMR90-X1

 has a small pool of virtual registers that show internal variables of the main processor. 

Some register values will be dependent upon the configuration settings of the 

DXMR90-X1. Do not use Read Rules to move 

Virtual Local Registers data into Local Registers. Use the Action Rule > Register Copy function to move Virtual Local Regis-
ters into Local Registers space (1-850). 

Modbus registers for virtual registers

Registers 

Definition 

 

10001 

GPS latitude direction (N, S, E, W) 

GPS Coordinate Data if the DXM is configured to read an external GPS unit. 

10002 

GPS latitude 

10003 

GPS longitude direction (N, S, E, W) 

10004 

GPS longitude 

 10011–10012 

Resync timer 

Engineering use 

 10013–10014 

Resync timer rollover 

Engineering use 

 10015–10016 

Reboot cause (Restart Codes above) 

Reboot Type 

 10017–10018 

Watchdog reset count 

Counter to track how many resets have been caused by the Watchdog 

 10025–10026 

Http Push SSL Acquires 

Statistical counts of connections, disconnections and forced disconnects when 

the 

DXMR90-X1

 creates a connection using SSL/TLS (Encrypted connections) 

 10027–10028 

Http Push SSL Releases 

 10029–10030 

Http Push SSL Forced Releases 

 10031–10032 

Http Push Attempts 

Statistical counts of connections, disconnections and forced disconnects when the 

DXM controller creates a connection using HTTP non-encrypted 

 10033–10034 

Http Push Successes 

 10035–10036 

Http Push Failures 

 10037–10038 

Http Push Last Status 

Last 

DXMR90-X1

 push status

0 = Initial state, no push attempt as finished yet 
1 = Attempt complete 
2 = Attempt aborted 

Continued on page 21

© Banner Engineering Corp.

Содержание DXMR90-X1 Series

Страница 1: ...DXMR90 X1 Series Controller Instruction Manual Banner Engineering Corp May 09 2023 www bannerengineering com...

Страница 2: ...dbus Slave IDs 25 Modbus Operation 26 Modbus Communication Timeouts 26 Modbus TCP Client 26 Chapter 5 Configuration Instructions Scheduler 27 Create a Weekly Event 27 Create a One Time Event 28 Create...

Страница 3: ...es for the DXMR90 X1 45 Chapter 8 Product Support and Maintenance Specifications for the DXMR90 X1 49 FCC Part 15 Class A 50 Industry Canada Statement for Intentional Radiators 50 File System and Arch...

Страница 4: ...Blank page 4...

Страница 5: ...view of the DXMR90 X1 Series Controller Configurable Modbus Port 0 female Modbus Master Ports 1 4 female Configurable Modbus Port 0 and Power male D coded Ethernet female One male M12 connection provi...

Страница 6: ...at include optional scaling error con ditions and the ability to activate a read rule Cyclical or Change of State Write rules to local wired Modbus devices with scaling Modbus TCP Master Read or Write...

Страница 7: ...XMR90 X1 as a slave device The slave Modbus RTU port allows access all the internal local registers concurrently with the master RTU port Port 0 can be con figured as a Modbus Master Port using the DX...

Страница 8: ...user can store 32 bit numbers Using Local Registers with external Modbus devices follows the Modbus standard of a 16 bit holding register Local Registers are accessible as Modbus ID 199 when using Scr...

Страница 9: ...s slave ID 203 Modbus Register LED Color State 2101 bit 0 LED 1 Green 1 On 0 Off 2102 bit 0 LED 2 Red 2103 bit 0 LED 3 Amber 2104 bit 0 LED 4 Amber 2105 bit 0 LED 5 Red 2106 bit 0 LED 6 Green Dimensio...

Страница 10: ...Blank page 10...

Страница 11: ...Pin Wire Color Description 2 3 4 1 5 1 Brown bn 12 V DC to 30 V DC 2 White wh RS485 D1 B 3 Blue bu DC common GND 4 Black bk RS485 D0 A 5 Gray gy Not used reserved CAUTION Wiring devices incorrectly w...

Страница 12: ...oftware refer to the instruction manual p n 209933 Overview of the configuration software features DXM Configuration Software Local Registers Register Mapping Action Rules Scheduler ScriptBasic System...

Страница 13: ...ct another model If the active configuration is incompatible with the selected model you will be prompt ed to either proceed and wipe out the active configuration or cancel the model change and preser...

Страница 14: ...e web server set Cloud Permissions to read If the Cloud Permissions are set to Read the web server only views data from the device and cannot write data to the device If the permissions are set to Wri...

Страница 15: ...Settings System screen to define the time zone and daylight saving option The time zone and DST options are saved into the configuration file Settings System Device Time Name your rule 4 Select the P...

Страница 16: ...8 hardware See the figure below to help in determining the minimum screw length Set the IP Address Launch the DXM Configuration Software 1 Go to the Settings Ethernet screen 2 In the IP Address sectio...

Страница 17: ...nual 17 3 mm for minimum engagement of three threads Screw Length 16 0 mm X mm 3 mm X 16 0 mm CAUTION Do not overtighten the DXMR90 X1 s mounting screw during installation Overtightening can affect th...

Страница 18: ...Blank page 18...

Страница 19: ...or the DXMR90 X1 are its Local Registers which can store 4 byte values that result from regis ter mapping action rules MicroPython or ScriptBasic commands Local Registers updated from Modbus transacti...

Страница 20: ...ng point number There are a total of 2000 floating point values they are addressed as two 16 bit pieces to accom modate the Modbus protocol Use these registers when reading writing external devices th...

Страница 21: ...success streak 11000 Read map success count Read Write maps statistics 12000 Write map success count 13000 Read map timeout count 14000 Write map timeout count 15000 Read map error count 16000 Write...

Страница 22: ...Port 0 4 5 pin M12 Connector female Pin Wire Color Description 2 3 4 1 5 1 Brown bn 12 V DC to 30 V DC 2 White wh RS485 D1 B 3 Blue bu DC common GND 4 Black bk RS485 D0 A 5 Gray gy Not used reserved...

Страница 23: ...devices The Timeout controls how long the DXMR90 X1 waits before determining a command failed to send Set based on the specific application requirements The Delay between messages defines the minimum...

Страница 24: ...May 09 2023 DXMR90 X1 Series Controller Instruction Manual 24 Slave Port 0 Settings Banner Engineering Corp...

Страница 25: ...slave IDs the DXMR90 X1 uses for its own Modbus network The DXM Modbus slave ID and other Mod bus slave port parameters are defined by using the configuration software The DXMR90 X1 operates the Modbu...

Страница 26: ...nsiderations need to be made to set the timeout parameter when the DXMR90 X1 is communicating to an external Modbus device through a serial data radio In general longer timeouts may be required to ens...

Страница 27: ...ent before the current time For screens that contain tables with rows click on any row to select it Then click Clone or Delete to copy paste or remove that row Create a Weekly Event Use the Scheduler...

Страница 28: ...specific or relative to sunrise or sunset Define one time events using the Sched uler One Time Events screen Scheduler One Time Events screen Create a Holiday Event Use the Scheduler Holidays screen t...

Страница 29: ...the Settings Cloud Services screen 1 In the upper right select Show advanced settings 2 Define the username and password in the Web Server Authentication section of the screen Web Server Authenticati...

Страница 30: ...low goes through the Local Registers which are data storage elements that reside within the processor Using the configuration software the controller can be programmed to move register data from the L...

Страница 31: ...ly add a Banner DXM device to the PLC Download the EDS files from the Banner website DXM EDS Configuration File for PLCs p n b_4205242 DXM EIP Config File for DXM Controller with Internal Gateway Mode...

Страница 32: ...in numerical order and placed into the data buffer destined for assembly instance 100 DXM local registers are capable of 32 bits but only the lower 2 bytes 16 bits for each local register are transfer...

Страница 33: ...plete the mail server authentication process After entering the user name and password click on Send SMTP Password to save the user name and password to the DXMR90 X1 The DXMR90 X1 must be connected t...

Страница 34: ...rameters From the Settings Notifications screen enter the SMTP definition login and password for a mail server To define the Ethernet IP address give the DXMR90 X1 a static IP address In most cases yo...

Страница 35: ...ecipients selected in the threshold definition for sending alert messages Define Threshold Rules for Email To define a threshold go to Local Registers Action Rules Thresholds Depending upon which reci...

Страница 36: ...al 36 Event Action Event based pushes caused by Action rules sent using email follow the same process when failures occur based on the network connection Email There are no retries for emails that fai...

Страница 37: ...s are plugged into slots In the PROFINET IO data model Slot 0 Subslot 1 is reserved for the Device Access Point DAP or network interface Configure the DXM Controller for a PROFINET IO Connection To us...

Страница 38: ...ill not be ap plied otherwise For example plugging in the 16 16 byte module to a slot corresponding to a device that has 22 bytes of PDO results in an error Process data sent from the PLC to DXM will...

Страница 39: ...x851 x851 x853 x853 x858 x859 Slot 10 ISDU Module ID Submodule ID Module Size bytes Register Start Register End Direction 0x4D 0x01 ISDU 190 Byte Status 196 351 442 Bidirectional 196 200 291 0x4E 0x0...

Страница 40: ...Install the GSD File Although these instructions are specific for the Siemens TIA Portal v14 software you may use these instructions as a basis for installing the GSD file into another controller Dow...

Страница 41: ...nage general station description file GSD The Install general station decription file window opens 7 Click the More options icon to the right of the Source path field and browse to the location the DX...

Страница 42: ...r Other field devices PROFINET IO Banner Engineering Corp Banner Launch the Siemens TIA Portal v14 software 1 Click Open existing project 2 Select a project and open it 3 Click Devices networks Networ...

Страница 43: ...restarted after it was discovered and configured by the PLC the DXM retains the IP address that was assigned to it using the LCD or software until after the PLC discovers the DXM and assigns it the sp...

Страница 44: ...another controller PLC Open a project and click on Devices networks The Network view displays 1 Right click on the DXM icon and select Assign device name The Assign PROFINET device name window display...

Страница 45: ...4 V DC 1 A output UL Listed Class 2 barrel jack connector SMBR90S Stainless steel bracket 4x M4 07 pemnuts B Includes 2x M4 stainless steel hex head screws and flat washers Hole center spacing A 40 B...

Страница 46: ...Length Style Dimensions Pinout Female MQDC1 501 5 0 5 m 1 5 ft Straight 44 Typ 14 5 M12 x 1 2 3 4 1 5 1 Brown 2 White 3 Blue 4 Black 5 Gray MQDC1 503 0 9 m 2 9 ft MQDC1 506 2 m 6 5 ft MQDC1 515 5 m 16...

Страница 47: ...ded Ethernet Model Length Style Dimensions Pinout Male STP M12D 406 1 83 m 6 ft Straight 47 4 Typ 14 5 M12 x 1 0 6g RJ45 1 White Orange 2 Orange 3 White Blue 6 Blue 4 2 3 1 1 White Orange 2 White Blue...

Страница 48: ...Blank page 48...

Страница 49: ...38 4k 57 6K or 115 2K Data format 8 data bits no parity 1 stop bit Communication Protocols Modbus RTU Modbus TCP EtherNet IP and PROFINET EtherNet IP is a trademark of ODVA Inc Modbus is a reg istered...

Страница 50: ...s Cet appareil contient des metteurs r cepteurs exempt s de licence conformes la norme Innovation Sciences et D veloppement conomique Canada L exploitation est autoris e aux deux conditions suivantes...

Страница 51: ...DXM Firmware updates and descrip tion details are found on the Banner website Customers with critical update requirements will get access to pre released firmware from the factory Website Information...

Страница 52: ...ng com pour les d tails sur leur utilisation correcte les applica tions les notes de s curit et les instructions de montage Install and properly ground a qualified surge suppressor when installing a r...

Страница 53: ...DEALING OR TRADE USAGE This Warranty is exclusive and limited to repair or at the discretion of Banner Engineering Corp replacement IN NO EVENT SHALL BANNER ENGINEERING CORP BE LIABLE TO BUYER OR ANY...

Страница 54: ...nstruction Manual 54 Document Information Document title Sure Cross DXMR90 X1 Series Controller Instruction Manual Part number 225859 Revision C Original Instructions Banner Engineering Corp All right...

Страница 55: ...LinkedIn Twitter Facebook 2023 All rights reserved www bannerengineering com...

Отзывы: