7 Product Support and Maintenance
7.1 Specifications
Supply Voltage
12 V DC to 30 V DC
Supply Protection Circuitry
Protected against reverse polarity and transient voltages
Power Consumption
24 V DC at 100 mA + 200 mA/port = 900 mA maximum
Construction
Connector Body: PVC translucent black
Indicators
Green/amber: Program status indicators
Green/amber: Ethernet communications
Red/green/blue on port 1: IO-Link Port 1 Status
Red/green/blue on port 2: IO-Link Port 2 Status
Red/green/blue on port 3: IO-Link Port 3 Status
Red/green/blue on port 4: IO-Link Port 4 Status
Connections
Five integral 5-pin M12 female quick disconnect
One integral 4-pin M12 male quick disconnect
One integral 5-pin M12 female D-Code quick disconnect
Application Note
When connecting external devices through the DXMR90-4K, it is
important not to exceed maximum current limitations of 3.5 Amps
Communication Protocols
Modbus
®
RTU, Modbus/TCP, EtherNet/IP
™
2
Communication Hardware (RS-485)
Interface: 2-wire half-duplex RS-485
Baud rates: 1.2K, 2.4K, 9.6k, 19.2k (default), 38.4k, 57.6K, or 115.2K
Data format: 8 data bits, no parity, 1 stop bit
Security Protocols
TLS, SSL, HTTPS
Digital Inputs (SIO [DI] Mode)
Input Current: 5 mA typical
ON Voltage/Current: 15 V DC minimum/5 mA minimum
OFF Voltage: 5 V DC maximum
Digital Outputs (SIO [DO] Mode)
On-Resistance: 120 mΩ typical, 250 mΩ maximum
Current Limit: 0.7 A minimum, 1.0 A typical, 1.3 A maximum
Off Leakage Current: -10 μA minimum, 10 μA maximum
IO-Link Baud Rates
COM1: 4.8 kbps
COM2: 38.4 kbps
COM3: 230.4 kbps
Environmental Ratings
For Indoor Use Only
IP65, IP67, NEMA 1, UL Type 1
Operating Conditions
–40 °C to +70 °C (–40 °F to +158 °F)
90% at +70 °C maximum relative humidity (non-condensing)
Storage Temperature
–40 °C to +80 °C (–40 °F to +176 °F)
Vibration and Mechanical Shock
Meets IEC 60068-2-6 requirements (Vibration: 10 Hz to 55 Hz, 1.0 mm
amplitude, 5 minutes sweep, 30 minutes dwell)
Meets IEC 60068-2-27 requirements (Shock: 30G 11 ms duration, half
sine wave)
Required Overcurrent Protection
WARNING:
Electrical connections must be
made by qualified personnel in accordance
with local and national electrical codes and
regulations.
Overcurrent protection is required to be provided by end product
application per the supplied table.
Overcurrent protection may be provided with external fusing or via
Current Limiting, Class 2 Power Supply.
Supply wiring leads < 24 AWG shall not be spliced.
For additional product support, go to www.bannerengineering.com.
Supply Wiring (AWG)
Required Overcurrent Protection (Amps)
20
5.0
22
3.0
24
2.0
26
1.0
28
0.8
30
0.5
7.2 File System and Archive Process
The DXM file system is in a serial EEPROM that stores non-volatile configuration information. The serial EEPROM stores
basic data that is required to be non-volatile, including network configuration data, IP address, MAC address, network masks,
firewall settings, and authentication information.
The controller XML configuration file created by the DXM Configuration Software is stored in EEPROM. The small section of
non-volatile local registers is also stored in EEPROM.
2
EtherNet/IP
™
is a trademark of ODVA, Inc. Modbus
®
is a registered trademark of Schneider Electric USA, Inc. PROFINET
®
is a registered trademark of PROFIBUS Nutzerorganisation
e.V.
DXMR90-4K IO-Link Master