13 Filter
All safe digital input modules are equipped with separately configurable switch-on and switch-off filters. The func-
tionality of the filters depends on the firmware version and is illustrated in the following table and figures:
Module type
Version
TOFF filter diagram
Filter time to be considered in addi-
tion to the total response time
I/O modules
<301
Diagram 1
2x TOFF filter time
SafeLOGIC-X
301, 311, 312
Diagram 1
2x TOFF filter time
I/O modules
≥301
Diagram 2
1x TOFF filter time
SafeLOGIC-X
302, ≥313
Diagram 2
1x TOFF filter time
input_signal
t_off_intern
t_off_User
t_on_User
TOF_0
TON_0
filtered_signal
IN
PT
Q
ET
IN
PT
Q
ET
Figure 15: SI input filter - Diagram 1
input_signal
t_off_intern
t_off_User
t_on_User
TOF
filtered_signal
IN
PT
Q
ET
IN
PT
Q
ET
IN
PT
Q
ET
reset
INT#2
Figure 16: SI input filter - Diagram 2
Key:
•
input_signal: Status of the input channel
•
filtered_signal: Filtered status of the input channel. This is used as an input for the PLCopen function block
and forwarded to the SafeLOGIC controller
•
t_off_intern: Internal parameter (5 ms) for suppressing "external" test pulses (only with
"Pulse Mode = External")
•
t_off_User: Parameter for the switch-off filter
•
t_on_User: Parameter for the switch-on filter
Unfiltered
The input state is collected with a fixed offset to the network cycle and transferred.