Installation • Installation
Chapter 3 Installation
Automation Panel 9x3 User's Manual V1.00
49
1.2 Replacing link modules
1. Disconnect the Automation Panel (unplug the power cable!). Isolate from all potential sources of electrical
power!
2. Discharge any electrostatic charge on the ground connection.
3. Remove the Automation Panel from the control cabinet. To do so, follow the steps in section "Mounting an
Automation Panel 9x3" on page 47 in reverse order.
4. Place the Automation Panel on a clean, flat surface.
5. Remove the Torx screws (T10) indicated in the following image.
Figure 29: Removing the Torx screws
6. The link module can now be removed by pulling it straight up.
Figure 30: Removing the link module
7. The link module can now be replaced by following these steps in reverse order. The maximum tightening
torque of the Torx screws (T10) is 0.5 Nm.