Installation  • Installation

Chapter 3 Installation

Automation Panel 9x3 User's Manual V1.00

47

Chapter 3 • Installation

1 Installation

Danger!

All supply voltage must be disconnected before removing device covers or components or
removing/installing accessories, hardware or cables.

The power cable must be disconnected from the device and from the voltage supply.

Before the device can be connected to the power supply and turned on, all covers, components,
accessories, hardware and cables must be installed or attached.

1.1 Mounting an Automation Panel 9x3

The Automation Panel 9x3 is mounted in the cutout using retaining clips. The number of retaining clips depends

on the display unit.

Installation notes

Environmental conditions must be taken into consideration.

When installed in an enclosed housing, enough space must be available for air to circulate sufficiently.

This device must be mounted to a flat, clean and burr-free surface.

This device is only certified for operation in closed rooms.

This device must not be subjected to direct sunlight.

Ventilation holes must not be covered.

This device must be mounted in one of the approved orientations.

The wall or control cabinet must be able to withstand four times the total weight of the device.

The flex radius of connected cables (DVI, SDL, USB, etc.) must not be exceeded.

This device must be mounted in a position that minimizes glare on the screen.

This device must be mounted in a position and orientation that make viewing as easy as possible for the
operator.

The thickness of the wall or cabinet plate must be between 1 mm and 6 mm.
A hex-head screwdriver is needed to tighten and loosen the screws on the retaining clips. The maximum torque

for the retaining clips is 1 Nm.
Devices must be installed on flat, clean and burr-free surface; uneven areas can cause damage to the display

when the screws are tightened or intrusion of dust and water.

Procedure

1. Check whether the included mounting screws are screwed into the retaining clips. If not, then the mounting

screws must be screwed into the retaining clips with a hex-head screwdriver. The mounting screws must only

be screwed in far enough that they no longer protrude above the retaining clip.

Retaining clips

Mounting screws

Figure 26: Prepare retaining clips

2. Insert the device into the front side of the smooth, flat installation cutout. The dimensions for the cutout can

be found under "Installation diagrams" on page 17.

Содержание MAAP9x3-ENG

Страница 1: ...date of publication however Bernecker Rainer Industrie Elektronik Ges m b H makes no warranty ex pressed or implied with regard to the products or documentation contained within this manual In additi...

Страница 2: ...2 Chapter 1 General information Chapter 2 Technical data Chapter 3 Installation Chapter 4 Standards and certifications Chapter 5 Accessories Chapter 6 Maintenance and service Appendix A...

Страница 3: ...escription of individual modules 12 1 2 1 Display units 12 1 2 2 Link modules 12 1 3 Structure Configuration 13 1 3 1 Configuration 13 2 Complete system 14 2 1 Connection options 14 2 1 1 SDL operatin...

Страница 4: ...4 5 Touch screen calibration 55 5 1 Single touch analog resistive 55 5 1 1 Windows 7 Professional Ultimate 55 5 1 2 Windows Embedded Standard 7 Embedded Premium 55 5 1 3 Windows XP Professional 55 5 1...

Страница 5: ...flex cables with extender 75 3 5 1 5CASDL 0xx0 13 75 3 6 USB cables 79 3 6 1 5CAUSB 00xx 00 79 3 7 RS232 cables 80 3 7 1 9A0014 xx 80 Chapter 6 Maintenance and service 82 1 Cleaning 82 2 Tips for ext...

Страница 6: ...General information Manual history 6 Automation Panel 9x3 User s Manual V1 00 Chapter 1 General information 1 Manual history Version Date Change 1 00 10 Dec 13 First version Table 1 Manual history...

Страница 7: ...es for proper ESD handling Electrical components with a housing Do not touch the connector contacts on connected cables Do not touch the contact tips on circuit boards Electrical components without a...

Страница 8: ...ng monitoring devices or uninterruptible power supplies it is necessary for certain parts to carry dangerous voltage levels over 42 VDC Touching one of these parts can result in a life threatening ele...

Страница 9: ...Separation of materials It is necessary to separate different materials so the device can undergo an environmentally friendly recycling process Component Disposal Programmable logic controllers Operat...

Страница 10: ...ent Caution Disregarding these safety guidelines and notices can result in injury or damage to equipment Information This information is important for preventing errors Table 3 Description of the safe...

Страница 11: ...30 m 75 5CASDL 0400 13 SDL flex cable with extender 40 m 75 5CASDL 0430 13 SDL flex cable with extender 43 m 75 Terminal blocks 0TB103 9 Connector 24 VDC 3 pin female 3 31 mm screw clamp protected ag...

Страница 12: ...een and form the basis for each Automation Panel 9x3 and Panel PC 900 System Different display sizes and touch screen technologies are available These display units can be operated exclusively as a co...

Страница 13: ...essential for operation as an Automation Panel 9x3 Display unit Link module Display unit Configuration Base system Select 1 5DLSDL 1001 00 SDL DVI receiver Link module Select 1 Select 1 Terminal block...

Страница 14: ...aces on the Automation Panel 9x3 9xD Panel In interface USB In x Supply voltage Brightness controls x USB1 USB2 USB 1 1 COM touch interface x Grounding Maximum cable length 40 m 2 1 1 2 SDL Operating...

Страница 15: ...Industrial PC Supply voltage Grounding Supply voltage Grounding Availability of interfaces on the Automation Panel 923 92D Panel In interface USB In USB 2 0 Supply voltage Brightness controls USB1 US...

Страница 16: ...touch 5AP923 1906 00 440 358 427 149 9 345 23 15 widescreen multi touch 5AP933 156B 00 414 258 5 401 105 5 9 245 5 20 18 widescreen multi touch 5AP933 185B 00 475 295 462 166 5 9 282 18 21 widescreen...

Страница 17: ...aining clips 12 single touch 5AP923 1215 00 304 228 1 6 10 pcs 15 single touch 5AP923 1505 00 359 277 1 6 10 pcs 19 single touch 5AP923 1906 00 429 347 1 6 12 pcs 15 widescreen multi touch 5AP933 156B...

Страница 18: ...intain the device this must be taken into consideration during instal lation Rear view Side view S1 S1 S4 S2 S2 S3 S3 Figure 5 Automation Panel 9x3 Spacing for air circulation S1 20 mm S2 50 mm S3 50...

Страница 19: ...e following sections C D A B 0 0 Figure 6 Automation Panel 9x3 Mounting orientation Mounting orientation Ambient temperature limitation 0 0 None A 90 counterclockwise None B 90 clockwise None C D 180...

Страница 20: ...15 00 2200 15 single touch 5AP923 1505 00 3700 19 single touch 5AP923 1906 00 5800 15 widescreen multi touch 5AP933 156B 00 3850 18 widescreen multi touch 5AP933 185B 00 4850 21 widescreen multi touch...

Страница 21: ...C per 1000 meters starting at 500 meters above sea level 5DLSDL 1001 00 Maximum ambient temperature 55 What else can also be operated at the max ambient temperature or are there any limits Temperature...

Страница 22: ...en establishing these limits Display type Model number Operation Storage Transport 12 single touch 5AP923 1215 00 5 to 90 5 to 90 15 single touch 5AP923 1505 00 8 to 90 8 to 90 19 single touch 5AP923...

Страница 23: ...on 2 3 4 Shock The following table provides an overview of the maximum shock specifications of the complete system The use of individual components may result in limitations Operation Storage Transpor...

Страница 24: ...C supply voltage Table 18 24 VDC supply voltage connection Electrical characteristics Nominal voltage 24 VDC 25 Nominal current Max 2 5 A Electrical isolation Yes Uninterruptible power supply No 2 4 2...

Страница 25: ...ck diagram shows the simplified structure of the 5DLSDL 1001 00 SDL DVI receiver link module for the Automation Panel 9x3 USB Type B USB Type A USB Type A Display data IN switches Panel Link receiver...

Страница 26: ...Automation Panel 9x3 1 2 3 4 5 6 7 8 9 Figure 9 Overview of interfaces Link module SDL DVI Receiver No Type of interface No Type of interface 1 Panel In SDL DVI Panel In interface 6 24 VDC power 24 VD...

Страница 27: ...olarity Pin Description 1 2 Functional ground 3 Model number Short description Terminal blocks 0TB103 9 Connector 24 V 5 08 3 pin screw clamp 0TB103 91 Connector 24 V 5 08 3 pin cage clamp 3 pin femal...

Страница 28: ...Hot plug detect 2 TMDS data 2 DVI lane 2 positive 17 TMDS data 0 DVI lane 0 negative 3 TMDS data 2 4 SHIELD Shield for data pair 2 and 4 18 TMDS data 0 DVI lane 0 positive 4 SDL SDL lane negative 19...

Страница 29: ...L 0100 00 5CASDL 0100 01 5CASDL 0100 03 15 5CASDL 0150 00 5CASDL 0150 01 5CASDL 0150 03 5CASDL 0150 00 5CASDL 0150 01 5CASDL 0150 03 5CASDL 0150 00 5CASDL 0150 01 5CASDL 0150 03 5CASDL 0150 00 5CASDL...

Страница 30: ...12 Mbit s high speed 480 Mbit s Current load2 USB1 USB2 A total of max 1 A Cable length USB 2 0 Max 5 m without hub 2x USB type A female USB2 USB1 Table 26 USB1 USB2 interfaces 1 The interfaces etc av...

Страница 31: ...FO Transfer rate Max 9600 baud Bus length Max 5 m Pin Assignment 1 NC 2 RXD 3 TXD 4 NC 5 GND 6 NC 7 RTS 8 CTS 9 NC 9 pin male DSUB connector 5 1 9 6 Table 28 COM Pinout 1 The interfaces etc available...

Страница 32: ...al 12 1 Colors 16 2 million Resolution XGA 1024 x 768 pixels Contrast 700 1 Viewing angles Horizontal Direction R Direction L 80 Vertical Direction U Direction D 80 Backlight Classification LED Bright...

Страница 33: ...tion Panel 9x3 User s Manual V1 00 33 3 1 1 4 Dimensions 315 239 Figure 12 5AP23 1215 00 Dimensions 3 1 1 5 Temperature humidity diagram Temperature C Operation Storage Transport Relative humidity RH...

Страница 34: ...lors 16 2 million Resolution XGA 1024 x 768 pixels Contrast 700 1 Viewing angles Horizontal Direction R Direction L 80 Vertical Direction U Direction D 70 Backlight Classification LED Brightness 350 c...

Страница 35: ...70 288 Figure 14 5AP23 1505 00 Dimensions 3 1 2 5 Temperature humidity diagram 0 0 10 20 30 40 50 60 70 80 90 80 70 60 50 40 30 20 10 5 10 100 95 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 Temper...

Страница 36: ...lors 16 7 million Resolution SXGA 1280 x 1024 pixels Contrast 2000 1 Viewing angles Horizontal Direction R Direction L 89 Vertical Direction U Direction D 89 Backlight Classification LED Brightness 30...

Страница 37: ...40 358 Figure 16 5AP23 1906 00 Dimensions 3 1 3 5 Temperature humidity diagram 0 0 10 20 30 40 50 60 70 80 90 80 70 60 50 40 30 20 10 5 10 100 95 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 Temper...

Страница 38: ...s 16 7 million Resolution HD 1366 x 768 pixels Contrast 500 1 Viewing angles Horizontal Direction R Direction L 85 Vertical Direction U Direction D 80 Backlight Classification LED Brightness 300 cd m...

Страница 39: ...4 258 5 Figure 18 5AP933 156B 00 Dimensions 3 1 4 5 Temperature humidity diagram 0 0 10 20 30 40 50 60 70 80 90 80 70 60 50 40 30 20 10 5 10 100 95 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 Temp...

Страница 40: ...16 7 million Resolution HD 1366 x 768 pixels Contrast 1000 1 Viewing angles Horizontal Direction R Direction L 170 Vertical Direction U Direction D 160 Backlight Classification LED Brightness 300 cd...

Страница 41: ...95 475 Figure 20 5AP933 185B 00 Dimensions 3 1 5 5 Temperature humidity diagram 0 0 10 20 30 40 50 60 70 80 90 80 70 60 50 40 30 20 10 5 10 100 95 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 Tempe...

Страница 42: ...rs 16 7 million Resolution FHD 1920 x 1080 pixels Contrast 1000 1 Viewing angles Horizontal Direction R Direction L 178 Vertical Direction U Direction D 178 Backlight Classification LED Brightness 250...

Страница 43: ...1 5 333 Figure 22 5AP933 215C 00 Dimensions 3 1 6 5 Temperature humidity diagram 0 0 10 20 30 40 50 60 70 80 90 80 70 60 50 40 30 20 10 5 10 100 95 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 Temp...

Страница 44: ...6 7 million Resolution FHD 1920 x 1080 pixels Contrast 5000 1 Viewing angles Horizontal Direction R Direction L 89 Vertical Direction U Direction D 89 Backlight Classification LED Brightness 300 cd m...

Страница 45: ...8 5 364 Figure 24 5AP933 240C 00 Dimensions 3 1 7 5 Temperature humidity diagram 0 0 10 20 30 40 50 60 70 80 90 80 70 60 50 40 30 20 10 5 10 100 95 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 Temp...

Страница 46: ...tness button Yes 1 Interfaces COM1 Type RS232 modem capable not electrically isolated Design 9 pin male DSUB connector Max baud rate 9 6 kbit s USB Quantity 3 2x Type A 1x Type B Type USB 2 0 Design 2...

Страница 47: ...n one of the approved orientations The wall or control cabinet must be able to withstand four times the total weight of the device The flex radius of connected cables DVI SDL USB etc must not be excee...

Страница 48: ...clips may vary depending on the display unit The exact number can be found in Table 7 Display units Installation diagrams on page 17 Figure 27 Inserting the retaining clips 4 Now fasten the retaining...

Страница 49: ...anel from the control cabinet To do so follow the steps in section Mounting an Automation Panel 9x3 on page 47 in reverse order 4 Place the Automation Panel on a clean flat surface 5 Remove the Torx s...

Страница 50: ...ion of 0 75 mm2 to 1 5 mm2 and wire end sleeves are to be used Installing the 0TB103 9 screw clamp terminal block Insert the wires with the wire end sleeves into the terminal contacts as shown in the...

Страница 51: ...ted Before connecting the mains cable it is important to make absolutely sure that it has been disconnected from the power source e g power supply 1 Touch the housing or ground connection in order to...

Страница 52: ...arantee safe conductance of electric disturbances the following points should be observed The device should be connected to the central grounding point in the control cabinet using the shortest route...

Страница 53: ...nstalling or connecting cables Information The maximum torque for the locating screws is 0 5 Nm Flex radius Locating screw Locating screw Figure 35 Flex radius Cable connection Information The specifi...

Страница 54: ...st be put into operation first before additional hardware is installed Caution Before the device is put into operation it must first be acclimated to room temperature It should not be immediately subj...

Страница 55: ...edded Standard 7 setup or if a an Automation Panel 800 900 9x3 has been connected after setup The necessary driver is available in the Downloads section of the B R website www br automation com 5 1 3...

Страница 56: ...b 3 Select the Automation Panel from the list 4 Set the desired brightness using the slider control Figure 36 Adjusting the display brightness Information Changes to these settings are displayed onlin...

Страница 57: ...as EN 61131 2 2007 Programmable logic controllers Part 2 Equipment requirements and tests EN 61000 6 2 2005 Electromagnetic compatibility EMC Part 6 2 Generic standards Immunity for industrial environ...

Страница 58: ...ds from organi zations such as ISO IEC and CENELEC as well as national standards from organizations such as UL CSA FCC VDE VE etc We are committed to ensuring the reliability of our products in an ind...

Страница 59: ...lamp pro tected against vibration by the screw flange 0TB103 91 Connector 24 VDC 3 pin female 3 31 mm cage clamp pro tected against vibration by the screw flange Table 45 0TB103 9 0TB103 91 Order data...

Страница 60: ...tage 300 V Nominal current 2 10 A contact Contact resistance 5 m Table 46 0TB103 9 0TB103 91 Technical data 1 Yes although applies only if all components installed within the complete system have this...

Страница 61: ...ost cases if the fdisk mbr command is additionally executed on the USB flash drive 2 1 2 Order data Model number Short description Figure USB accessories 5MMUSB 2048 01 USB 2 0 flash drive 2048 MB B R...

Страница 62: ...eak Shock Operation Max 1500 g peak Storage Max 1500 g peak Transport Max 1500 g peak Altitude Operation Max 3048 m Storage Max 12192 m Transport Max 12192 m Mechanical characteristics Dimensions Widt...

Страница 63: ...GL Yes 1 Cable structure Wire cross section AWG 28 Shielding Individual cable pairs and entire cable Cable shielding Tinned copper mesh optical coverage 86 Outer sheathing Material PVC Color Beige La...

Страница 64: ...1 1 4 Flex radius specifications Male connector Ferrite Ferrite Ferrite Flex radius Connector Ferrite bead Flex radius Ferrite bead Ferrite bead Figure 39 Flex radius specifications 3 1 1 5 Dimension...

Страница 65: ...le cable yourself it should be wired according to these specifications If a self built cable is used B R cannot guarantee that it will function properly All cables provided by B R are guaranteed to fu...

Страница 66: ...Individual cable pairs and entire cable Cable shielding Tinned copper mesh optical coverage 85 Outer sheathing Material PVC Color Black Labeling E74020 C UL AWM STYLE 20176 80 C 30V VW 1 DVI DIGITAL L...

Страница 67: ...1 00 67 3 2 1 4 Flex radius specifications Male connector Ferrite Ferrite Ferrite Flex radius Connector Ferrite bead Flex radius Ferrite bead Ferrite bead Figure 42 Flex radius specifications 3 2 1 5...

Страница 68: ...e yourself it should be wired according to these specifications If a self built cable is used B R cannot guarantee that it will function properly All cables provided by B R are guaranteed to function...

Страница 69: ...cture Wire cross section AWG 28 AWG 24 Shielding Individual cable pairs and entire cable Cable shielding Tinned copper mesh optical coverage 85 Outer sheathing Material PVC Color Black Connector Type...

Страница 70: ...1 4 Flex radius specifications Male connector Ferrite Ferrite Ferrite Flex radius Connector Ferrite bead Flex radius Ferrite bead Ferrite bead Figure 45 Flex radius specifications 3 3 1 5 Dimensions...

Страница 71: ...itable cable yourself it should be wired according to these specifications If a self built cable is used B R cannot guarantee that it will function properly All cables provided by B R are guaranteed t...

Страница 72: ...L 0300 03 General information Certification CE Yes cULus Yes GL Yes 1 Cable structure Wire cross section AWG 24 control wires AWG 26 DVI USB data Properties Silicone and halogen free Shielding Individ...

Страница 73: ...r ferrite bead ferrite bead tested 300 000 cycles with 15x cable diameter 4800 cycles hour Drag chain data Flex cycles 300 000 Velocity 4800 cycles hour Flex radius 180 mm 15x cable diameter Hub 460 m...

Страница 74: ...ions If a self built cable is used B R cannot guarantee that it will function properly All cables provided by B R are guaranteed to function properly Pinout DVI 24 1 male DVI 24 1 male Cable shield Ca...

Страница 75: ...control wires AWG 26 DVI USB data Properties Silicone and halogen free Shielding Individual cable pairs and entire cable Cable shielding Aluminum clad foil tinned copper mesh Outer sheathing Material...

Страница 76: ...ith 15x cable diameter 4800 cycles hour Drag chain data Flex cycles 300 000 Velocity 4800 cycles hour Flex radius 180 mm 15x cable diameter Hub 460 mm Weight Approx 5430 g Approx 7200 g Approx 7790 g...

Страница 77: ...itable cable yourself it should be wired according to these specifications If a self built cable is used B R cannot guarantee that it will function properly All cables provided by B R are guaranteed t...

Страница 78: ...flex cables with an extender must be connected between the B R Industrial PC and the Automation Panel display unit in the correct direction The proper signal direction is indicated on the extender B R...

Страница 79: ...rmation Certification CE Yes cULus Yes Cable structure Wire cross section AWG 24 28 Shielding Entire cable Outer sheathing Color Beige Connector Type USB type A male and USB type B male Mechanical cha...

Страница 80: ...with touch screen 5 m 9A0014 10 RS232 extension cable for remote operation of a display unit with touch screen 10 m Table 62 9A0014 02 9A0014 05 9A0014 10 Order data 3 7 1 3 Technical data Product ID...

Страница 81: ...le cable yourself it should be wired according to these specifications If a self built cable is used B R cannot guarantee that it will function properly All cables provided by B R are guaranteed to fu...

Страница 82: ...intended functions from being triggered when handling the touch screen or pressing keys This device should be cleaned with a moist cloth The cloth should be moistened with water and detergent a screen...

Страница 83: ...the only cause of screen burn in Screen burn in is also referred to as burn in effect image retention memory effect memory sticking or ghost image There are basically two types Area type This type of...

Страница 84: ...his stands for a value that has not been defined This may be be cause a cable manufacturer does not provide certain technical data for example NO Normally open A N O relay contact TBD To be defined Us...

Страница 85: ...imensions 45 Figure 25 5AP933 240C 00 Temperature humidity diagram 45 Figure 26 Prepare retaining clips 47 Figure 27 Inserting the retaining clips 48 Figure 28 Fasten retaining clips 48 Figure 29 Remo...

Страница 86: ...ble 31 5AP923 1505 00 Order data 34 Table 32 5AP923 1505 00 Technical data 34 Table 33 5AP923 1906 00 Order data 36 Table 34 5AP923 1906 00 Technical data 36 Table 35 5AP933 156B 00 Order data 38 Tabl...

Страница 87: ...cables Structure 74 Table 58 5CASDL 0300 13 5CASDL 0400 13 5CASDL 0430 13 Order data 75 Table 59 5CASDL 0300 13 5CASDL 0400 13 5CASDL 0430 13 Technical data 75 Table 60 5CAUSB 0018 00 5CAUSB 0050 00 O...

Страница 88: ...CASDL 0018 01 69 5CASDL 0018 03 72 5CASDL 0050 00 66 5CASDL 0050 01 69 5CASDL 0050 03 72 5CASDL 0100 00 66 5CASDL 0100 01 69 5CASDL 0100 03 72 5CASDL 0150 00 66 5CASDL 0150 01 69 5CASDL 0150 03 72 5CA...

Страница 89: ...ors 22 Vibration 23 Weight specifications 20 B backlight 31 83 brightness 31 Brightness controls 31 C Cable connections 53 Cables 63 DVI cables 63 SDL cables 66 SDL cables with 45 male connector 69 SD...

Страница 90: ...functional ground 27 52 G General tolerance 10 ground connection 27 52 Grounding 27 52 Guidelines 10 I immunity to disturbances 52 Installation Link module 49 Installation notes 47 Installing the DC m...

Страница 91: ...83 SDL cables 66 SDL cables with 45 male connector 69 SDL flex cables 72 SDL flex cables with extender 75 SDL operating mode 14 Mode 1 14 Mode 2 14 SDL resolution 29 serial interface 31 service life o...

Отзывы: