Automatic setting of the 100% fill level
The 100% point can be adjusted to the conditions on site via the setting menu.
1.) Install MEMPRO S6.6 / MEMPRO C S6.6 in tank!
The measuring tube must not stand on the tank bottom or be immersed in solid bottom mud!
2.) Fill the tank to a level of 50...100%!
The optimum is when the tank is filled to 100%!
3) Switch on the power supply!
4) Wait approx. 10 seconds until the unit is ready for operation!
5) Press the rotary/push switch for 3 seconds until the digital display is blinking!
6) Set the % filling level by turning the rotary/pressure switch ±!
7) Press the rotary/push switch again or wait 10 seconds until the digital display stops blinking.
The unit has calculated and permanently saved the 100% fill level.
Please note:
The measuring tube or the measuring hose must not be shortened at will!
The minimum length must not be less than 20% of the max. measuring range!
If the measuring tube/hose is too short, the 100% value can no longer be calculated correctly and is therefore limited in the evaluation
software.
Measuring cell type
Measuring range
Minimum tube/hose length
Type 1
0...1000mm water column
200mm
Type 2
0...2500mm water column
500mm
Type 4
0...4000mm water column
800mm
Measuring cell type → see type plate
Example:
MEMPRO C S6.6 R 1 2 X L = 1800mm
The 2 stands for the measuring cell type.
Overflow indicator
Measuring signal> 105% value → Digital display = ппп
Measuring signal< -5% value → Digital display = uuu
No measuring signal from sensor → Digital display = Err
SETTING THE LIMIT SWITCHING POINTS A1...A4
1) Press the rotary/push switch 1x until A1 is displayed (LED A1 is blinking)!
2) Press the rotary/push switch again!
3) Set limit switching point 1 with rotary/pressure switch (2...100%, factory setting = 80%)!
4.) Press the rotary/push switch again!
5) Set the delay time!
6) Press the rotary/push switch again!
7) Set hysteresis!
8) Press the rotary/push switch again!
9.) Set normally closed/ normally open contact!
10) Press the rotary/push switch again!
Back to menu level 1
All other values can be selected and set in the same way (see figure "SETTING MENU").
The limit value switching points A1...A4 and the clock pulse generator are selected in menu level 1 (press the rotary/push switch 1x and select
with right/left).
If no setting is made for longer than approx. 10 seconds, the display jumps back to the current level and the setting values are permanently
saved.
SETTING THE CLOCK GENERATOR
Relay A4 can alternatively be used as a clock generator - however, this renders the setting values of the limit relay A4 ineffective!
Pump time (ON time):
Set the time so that, depending on the length of the measuring tube and the supply hose, air bubbles escape from the bottom of the measuring
tube for approx. 3...5 seconds during each pumping process!
Pause time (OFF time):
For liquids that can clog the measuring tube due to deposits, pumping should be carried out as required.
If the temperature of the liquid fluctuates, more frequent pumping will reduce the drift of the measured value.
In most cases, it is sufficient to pump for approx. 30 seconds once or twice a day.
SETTING THE CLOCK GENERATOR (continuation)
The clock is switched on as soon as the ON and OFF time is set greater than 0.