OPERATING ELEMENTS
Combined rotary / press switch
Turn:
In menu level 1, relay 1...4 is selected.
The desired value is set in menu level 2...6.
Press:
To select the submenus.
A detailed view of the setting menu can be found under the item "SETTING MENU" in this manual.
Output relay A1...A4:
Relays 1...3 are limit relays.
Relay 4 can be used as a limit relay or alternatively as a clock generator for ventilation (see "SETTING THE CLOCK").
LEDs
LED lights up → relay has energised → contact closed
Limit switching point
Setting range 2...100% (related to the selected 100% level)
Factory setting: A1: 80%, A2: 60%, A3: 40%, A4: 20%
Delay time
Setting range 0.1...9.9 seconds
After exceeding/falling below the set limit value, the delay time is waited for, then the relay is switched.
Factory setting: 0.1 seconds
Hysteresis
Setting range: 1...99%
The output relay only drops out again when the measured value has fallen below the selected % value (factory setting 1%).
NC/NO contact selection
NO = normally open: The contact is open as long as the level is lower than the set limit value.
NC = normally closed: The contact is closed as long as the fill level is lower than the set limit value.
Factory setting: NO
Note: In the event of a power failure, all relay contacts are open!
VENTILATION CONNECTION
The ventilation connection is closed by a yellow protective cap with an internal seal.
Do not remove the protective cap during normal operation
It must only be removed if the MEMPRO is operated with the MEMPRO BL ventilation device.
Alternatively, an oil-free compressed air connection (max. 2bar) available on site can be used.
A pulse control is integrated in the electronics; e.g. a solenoid valve can be controlled by relay 4.
Ventilation connection
COMMISSIONING
LEV
05-09-2023
M-592.03-EN-AB
592-03
/3
HYDROSTATIC MULTIPLE
LIMIT VALUE SWITCH
MEMPRO S6.6