MAINTENANCE
Analyse combustion gases and check that the emission values are
correct at least once a year, in compliance with current law.
•
Clean air dampers, the air pressure switch with pressure port and
the relevant pipe, if any.
•
Check the electrode condition. Replace them, if necessary.
•
Clean the photocell. Replace it, if necessary.
•
Have the burner and the chimney cleaned by specialised person
-
nel (stove repairer); a clean burner is more efficient, lasts longer
and is quieter.
•
Check that the fuel filter is clean. Replace it, if necessary.
•
Check that all components of the combustion head are in good
condition, have not been deformed and are free from impurities
or deposits deriving from the installation environment and/or from
combustion.
•
Analyse combustion gases and check emissions values.
If it is necessary to clean the outside of the combustion head, take out
its components according to the procedure described:
•
Disconnect the diesel hoses (24) from the connectors beneath the
head unit (mind the dripping).
•
Undo the two screws (11) and turn the burner around the pin (10)
inside the specific hinge (figure 1).
•
After pulling out the ignition cables (14) from the relating electro
-
des, undo completely the locking nuts (6) from mixing unit.
•
Lift up the mixing unit (18) until the pipes come out and then pull
the mixing unit out completely in the direction indicated by the
arrow.
•
Complete the maintenance operations, proceed with the assem
-
bly of the mixing unit by carrying out the above operations in
reverse order, after checking that the ignition electrodes and the
flame disk are correctly positioned.
DANGER / ATTENTION
When closing the burner, gently pull the two ignition cables
towards the electrical panel, putting them slightly in tension, then
arrange them in their housing on the scroll. This will ensure that
the two cables do not get damaged by the fan during burner
operation.
10
11
24
0002935140
Fig.1
6
14
0002935150
18
0002935160
0002935170
34 / 44
0006081053_202301
ENGLISH
Содержание TBL 360P
Страница 2: ......
Страница 42: ...SCHEMI ELETTRICI TBL 85 105 130 160 210 260 P DACA 40 44 0006081053_202301 ITALIANO...
Страница 43: ...TBL 85 105 130 160 210 260 P 41 44 0006081053_202301 ITALIANO...
Страница 44: ...TBL 360 P DACA 42 44 0006081053_202301 ITALIANO...
Страница 45: ...TBL 360 P 43 44 0006081053_202301 ITALIANO...
Страница 86: ...WIRING DIAGRAMS TBL 85 105 130 160 210 260 P DACA 40 44 0006081053_202301 ENGLISH...
Страница 87: ...TBL 85 105 130 160 210 260 P 41 44 0006081053_202301 ENGLISH...
Страница 88: ...TBL 360 P DACA 42 44 0006081053_202301 ENGLISH...
Страница 89: ...TBL 360 P 43 44 0006081053_202301 ENGLISH...
Страница 91: ......