MODEL
TBL 210P / P DACA TBL 260P / P DACA
TBL 360P
TBL 360P DACA
Minimum flow rate
Kg/h
67
80
84
84
Maximum flow rate
Kg/h
177
219
304
304
Minimum thermal power
kW
800
950
1000
1000
Maximum thermal power
kW
2100
2600
3600
3600
³) emissions
mg/kWh
Class 1
Class 1
Class 1
Class 1
Viscosity
1.5° E - 20° C
1.5° E - 20° C
1.5° E - 20° C
1.5° E - 20° C
Operation
Two-stage
Two-stage
Two-stage
Two-stage
50hz transformer
10 kV - 30 mA
12kV - 35 mA
12kV - 35 mA
12kV - 35 mA
60hz transformer
-
-
12kV - 35 mA
12kV - 35 mA
50hz fan motor
kW
3
5.5
7.5
7.5
60hz fan motor
kW
-
-
9.2
9.2
50Hz three-phase electrical data
3L - 400V - 6.3A -
3.49kW
3L - 400V - 10.2A -
6.14kW
3L - 400V - 13.7A -
8.36kW
3L - 400V - 13.7A -
8.36kW
60Hz three-phase electrical data
-
-
3L - 380V - 17.5A -
10.13kW
3L - 380V - 17.5A -
10.13kW
50Hz single-phase electrical data
1N - 230V - 1.89A -
0.435kW
1N - 230V - 2.74A -
0.631kW
1N - 230V - 2.68A -
0.617kW
1N - 230V - 2.71A -
0.623kW
60Hz single-phase electrical data
-
-
1N - 220V - 2.8A -
0.617kW
1N - 220V - 2.8A -
0.617kW
Protection rating
IP44
IP40
IP40
IP40
Control box
LMO 44
LMO 44
LMO 44
LMO 44
Flame detection
Photoresistor
Photoresistor
Photoresistor
Photoresistor
Air flow rate regulation
hydraulic jack / servo
-
motor
hydraulic jack / servo
-
motor
hydraulic jack / servo
-
motor
hydraulic jack / servo
-
motor
Operating ambient air temperature
°C
-15 ÷ +40
-15 ÷ +40
-15 ÷ +40
-15 ÷ +40
Sound pressure**
dBA
-
87
87
87
Weight with packaging
kg
94
105
115
120
Weight without packaging
kg
89
94
105
110
Lower calorific power:
Diesel fuel: Hi = 11.86 kWh/kg = 42.70 Mj/kg
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory environment
conditions and cannot be compared to measurements carried out in different locations. Measurement accuracy σ = +/- 1.5 dB(A).
³) DIESEL EMISSIONS
Classes defined according to EN 267 standards.
Class
NOx emissions in mg/kWh diesel
fuel
CO emissions in mg/kWh diesel
fuel
1
≤ 250
≤ 110
2
≤ 185
≤ 110
3
≤ 120
≤ 60
7 / 44
0006081053_202301
ENGLISH
Содержание TBL 360P
Страница 2: ......
Страница 42: ...SCHEMI ELETTRICI TBL 85 105 130 160 210 260 P DACA 40 44 0006081053_202301 ITALIANO...
Страница 43: ...TBL 85 105 130 160 210 260 P 41 44 0006081053_202301 ITALIANO...
Страница 44: ...TBL 360 P DACA 42 44 0006081053_202301 ITALIANO...
Страница 45: ...TBL 360 P 43 44 0006081053_202301 ITALIANO...
Страница 86: ...WIRING DIAGRAMS TBL 85 105 130 160 210 260 P DACA 40 44 0006081053_202301 ENGLISH...
Страница 87: ...TBL 85 105 130 160 210 260 P 41 44 0006081053_202301 ENGLISH...
Страница 88: ...TBL 360 P DACA 42 44 0006081053_202301 ENGLISH...
Страница 89: ...TBL 360 P 43 44 0006081053_202301 ENGLISH...
Страница 91: ......