IONISATION CURRENT MEASUREMENT
To measure the ionisation current, remove the jumper between
terminals 30-31 on the printed circuit with the burner off.Connect
the microammeter terminals to the terminals. The microammeter
terminals must have a suitable scale to have the burner restart.
Once the flame has appeared it will be possible to measure the
ionisation current, the minimum value of which is shown in the
specific wiring diagram, to ensure the operation of the equipment.
At the end of the measurement, connect the jumper that has been
disconnected.
The minimum ionisation current needed to run the equipment is 6
µA.The burner flame generates a significantly higher current, which
usually does not require any control by the equipment.Should the
ionisation current need to be measured, a microammeter must be
connected in series to the ionisation electrode lead by opening the
connector “C”, see wiring diagram.
0002935683_45_60
A
B
C
D
TBG 45
4
5
4
4
TBG 60
4
9
4
4
1 - Ionisation electrode
2 - Ignition electrode
3 - Flame disk
4 - Mixer
5 - Gas delivery pipe
E - WARNING: central nozzle hole outlet near the electrode tip.