DESCRIPTION OF TBG 45 / 60 OPERATION
When the main switch and the I/O switch -10 on the electrical
panel are turned on, if the thermostats are on, voltage reaches the
command and control device, which starts up the burner (LED 7
comes on).
This turns on the fan motor for preventilation of the combustion
chamber.
The ignition transformer then comes on, and 2 seconds later the
gas valves open.
The main valve, which has two stages, has a device for adjusting
gas delivery for the first and second flame.The safety valve is an
ON/OFF valve.
The combustion air can be regulated manually using the air shut
-
ter (see section "Single stage air burner regulation diagram”).
As the burner is ON/OFF, the position of the air shutter must be
regulated for operation at maximum flow rate.
The presence of the flame, detected by the control device, per
-
mits continuation and completion of ignition, turning off the ignition
transformer.
The second flame then comes on (the second stage in the main
valve opens).
If there is no flame, the appliance shuts down in "safety lock-out"
mode (LED 8 comes on) within 3 seconds of the opening of the
first flame on the main valve.
In “safety lock-out” mode the valves are closed again immediately.
To reset the appliance from safety lock-out mode, press button -9
on the electrical panel.