APPLICATION OF THE BURNER TO BOILER
The burner is equipped with a mounting flange which slips
on the burner head. When applying the burner to the boiler,
it is necessary to
correctly position
the flange so that the
burner head enters the furnace
to the extent specified
by the boiler manufacture.
When the burner has been
correctly fastened to the boiler, proceed with connecting in
to the gas pipeline. The dimensions of the gas adduction
pipeline should be in function with it’s length and with gas
delivery according to UNI regulations. It must be perfectly
hermetic and adequately tested before the burner is general
inspection. It is indispensable to install a suitable pipe union
in the pipeline, in proximity to the burner, to allow for easy
disassembly of the burner and opening of the boiler door.
The DUNGS mod. MB... valve incorporates a filter and a
gas pressure stabilizer and, therefore, only a cut-off cock
and an anti-vibration joint have to be fitted onto the gas
adduction pipeline. Only if the gas pressure were above
the maximum value allowed by regulations (400 mm. W.C.)
would it be necessary to install a pressure reducer on the
gas pipeline outside the heating plant. We advise installing
a bend directly onto the burner gas ramp before applying
the removable fitting. This layout makes it possible to open
the boiler door, if there is one, after the fitting itself has been
opened. The above is clearly illustrated in the following
drawing (see BT 8871/GB).
ENGLISH
Boiler
Anti-vibration
joint
Pipe fitting
Vanne gas DUNGS multibloc
Burner
Door opening direction
Door
Gate
UPPER VIEW
BT 8871
00029
3
27
3
0
Insulating flange
Aluminium flange
Sheet metalring
Insulating Cord
FITTING THE BURNER TO THE BOILER
The burner is fitted with a sliding attachment flange on the combustion head.
All the components supplied must be mounted following the burner instructions.
When the burner is being mounted on the boiler it is necessary to place this flange in the right position to have the
combustion head enter the combustion chamber according to the boiler manufacturer’s requirements.
Light oil pipes must be connected to the burner after it has been properly mounted on the boiler.