11 / 36
0006080095_201207
ENGLISH
SIPHON FEED SYSTEM WITH FEED FROM THE TOP OF THE TANK
SUCTION FEED SYSTEM
GRAVITY FEED SYSTEM
Dimension P = 3,5 m. (max.)
H - Height difference between minimum fuel tank level and pump axis.
L - Total length of pipeline, including vertical lenght. Subtract 0,25 mt.
for every elbow or gate valve.
N.B. Comply with existing regulations regarding apparatus required in the pipeline system
1 Tank
2 Feeding pipe
3 Wire-net filter
4 Pump
5 Degasifier
6 Suction pipe
7 Return pipe
8 Automatic fuel interception
device at burner shut off
9 Non-return valve
Pump axis
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
8 Automatic fuel interception
device at burner shut off
9 One-way valve
10 Bottom valve
Pump axis
Pump axis
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
10 Bottom valve
TABLE OF PIPELINE FOR COMIST 180
H
Total lenght
meters
meters
Ø i. 16 mm.
Ø i. 18 mm.
1
30
40
1,5
35
45
2
35
45
2,5
40
50
3
40
50
H
Total lenght
meters
meters
Ø i. 16 mm.
Ø i. 18 mm.
1
30
40
1,5
35
45
2
35
45
2,5
40
50
3
40
50
H
Total lenght
meters
meters
Ø i. 16 mm.
Ø i. 18 mm.
0,5
21
34
1
18
29
1,5
15
24
2
11,5
19
2,5
8,5
14
3
5,5
9
3,5
-
3,5
Содержание COMIST 180
Страница 2: ......
Страница 36: ...34 36 0006080095_201207 ITALIANO SCHEMA ELETTRICO...
Страница 38: ...36 36 0006080095_201207 ITALIANO...
Страница 72: ...34 36 0006080095_201207 ENGLISH WIRING DIAGRAM...
Страница 74: ...36 36 0006080095_201207 ENGLISH...
Страница 108: ...34 36 0006080095_201207 ESPA OL ESQUEMA ELECTRICO...
Страница 110: ...36 36 0006080095_201207 ESPA OL...
Страница 144: ...34 36 0006080095_201207 FRAN AIS SCH MA LECTRIQUE...
Страница 146: ...36 36 0006080095_201207 FRAN AIS...
Страница 147: ......