TECHNICAL SPECIFICATIONS
MODEL
BTG 3,6P
BTG 6P
BTG 11P
Type-approval PIN
CE0085BQ0476
CE0085BQ0476
CE0085BQ0476
Maximum natural gas heat power
kW
41.9
56.3
99
Minimum natural gas heat power
kW
16.3
30.6
48.8
¹) natural gas emissions
mg/kWh
Class 2
Class 2
Class 2
Operation
Two-stage
Two-stage
Two-stage
50 Hz natural gas transformer
15kV - 25mA
15kV - 25mA
15kV - 25mA
60 Hz natural gas transformer
15kV - 25mA
15kV - 25mA
15kV - 25mA
Maximum natural gas heat rate
Stm³/h
4.2
5.7
10
Minimum natural gas heat rate
Stm³/h
1.6
3.1
4.9
Maximum natural gas pressure
hPa (mbar)
360
360
360
Minimum natural gas pressure
hPa (mbar)
19
20
20
Maximum propane thermal power
kW
41.9
56.3
99
Minimum propane thermal power
kW
16.3
30.6
48.8
Maximum propane thermal flow rate
Stm³/h
1.63
2.2
3.87
Minimum propane thermal flow rate
Stm³/h
0.64
1.2
1.9
Maximum propane pressure
hPa (mbar)
360
360
360
Minimum propane pressure
hPa (mbar)
30
30
30
²)propane emissions
mg/kWh
Class 2
Class 2
Class 2
50hz fan motor
kW
0.11
0.11
0.11
50hz fan motor rpm
r.p.m.
2800
2800
2800
60hz fan motor
kW
0.11
0.11
0.11
60hz fan motor rpm
r.p.m.
3300
3300
3300
Absorbed electrical power* 50hz
kW
0.11
0.11
0.11
Absorbed electrical power* 60hz
kW
0.11
0.11
0.11
50 Hz power supply voltage
1N~ 230V ± 10%
1N~ 230V ± 10%
1N~ 230V ± 10%
60 Hz power supply voltage
1N~ 220V ± 10%
1N~ 220V ± 10%
1N~ 220V ± 10%
Protection rating
IP40
IP40
IP40
Flame detection
IONISATION PROBE
IONISATION PROBE
IONISATION PROBE
Control box
LME21..
LME21..
LME21..
Operating ambient air temperature
°C
-15 ÷ +40
-15 ÷ +40
-15 ÷ +40
Sound pressure**
dBA
64
64
64
Calorific power below reference conditions 15° C, 1013 hPa (mbar):
Natural gas: Hi = 9,45 kWh/Stm³ = 34,02 MJ/Stm³
Propane: Hi = 24,44 kWh/Stm³ = 88,00 MJ/Stm³
For different types of gases and pressure values, contact our sales departments.
Minimum gas pressure, depending on the type of gas train used for obtaining max. flow rate with null pressure in the combustion chamber.
* Total absorption at start-up with ignition transformer on.
The measurements have been carried out in accordance with EN 15036 - 1 standard.
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory environment
conditions and cannot be compared to measurements carried out in different locations.
Propane / natural gas CO emissions ≤ 100 mg/kWh
Classes defined according to EN 676 standards.
¹) NATURAL GAS EMISSIONS
Class
NOx emissions in mg/kWh natural
gas
1
≤ 170
2
≤ 120
3
≤ 80
²) PROPANE GAS EMISSIONS
Class
NOx emissions in mg/kWh propane
gas
1
≤ 230
2
≤ 180
3
≤ 140
ENGLISH
5 / 30
0006080763_201912