WRONG ADJUSTMENT
Combustion head
Air passageway
wide open
Combustion head fastening and control
knobs
Combustion air inlet with gate
almost completely closed
CORRECT ADJUSTMENT
Air passageway fairly
closed.
Attention:
Do not
close completely
DIAGRAM ILLUSTRATING PRINCIPLE OF AIR CONTROL
Disc
Combustion head
Disc
Combustion head fastening and control
knobs
AIR REGULATION ON THE
COMBUSTION HEAD
The combustion head is provided with a regulation device that closes
(forward movement) or opens (backward movement) the air passage
between disc and head.
The passage closure increases the pressure upstream of the disc
also for low flow rates. The high speed and turbulence of the air
provides for its greater penetration into the fuel and therefore an
excellent mixture and flame stability. It can be indispensable to have
high air pressure upstream of the disc to prevent flame pulsations.
This condition is practically indispensable when the burner works
with a furnace that is pressurized and/or has a high heat load.
In practice, start by adjusting the device that closes the air on the
combustion head to an intermediate position, turning on the burner
for a preliminary adjustment.
When the maximum required supply is reached, correct the position
of the device closing the air on the combustion head by moving
it forwards or backwards so as to have a suitable air flow for the
delivery, with suction air adjustment shutter sensibly open.
When reducing the air passage on the combustion head, make sure
not to completely close it. Perfectly center the combustion head with
respect to the disc. A combustion head not perfectly centered to the
disc could lead to a wrong combustion and overheat the same head
causing its early wearing. Check it by looking through the inspection
hole on the burner rear side, and then fully tighten the screws that
lock the air regulation device on the combustion head.
Check that ignition is correct because if the regulator is shifted
forward, the outgoing air speed may be too high to permit
ignition. If this happens, gradually move the regulator back to
a position in which ignition takes place correctly, and accept
this as the final position.
Содержание BT 300 DSG 4T
Страница 2: ......
Страница 24: ...22 26 0006081081_201406 0002211530N2 ITALIANO SCHEMA ELETTRICO...
Страница 26: ...24 26 0006081081_201406 ITALIANO SCHEMA ELETTRICO...
Страница 28: ...26 26 0006081081_201406 ITALIANO...
Страница 50: ...22 26 0006081081_201406 0002211530N2 ENGLISH WIRING DIAGRAM...
Страница 52: ...24 26 0006081081_201406 ENGLISH WIRING DIAGRAM...
Страница 54: ...26 26 0006081081_201406 ENGLISH...
Страница 76: ...22 26 0006081081_201406 0002211530N2 ESPA OL ESQUEMA EL CTRICO...
Страница 78: ...24 26 0006081081_201406 ESPA OL ESQUEMA EL CTRICO...
Страница 80: ...26 26 0006081081_201406 ESPA OL...
Страница 102: ...22 26 0006081081_201406 0002211530N2 FRAN AIS...
Страница 104: ...24 26 0006081081_201406 FRAN AIS SCHEMA ELECTRIQUE...
Страница 106: ...26 26 0006081081_201406 FRAN AIS...
Страница 128: ...22 26 0006081081_201406 0002211530N2 DEUTSCH...
Страница 130: ...24 26 0006081081_201406 DEUTSCH SCHALTPLAN...
Страница 132: ...26 26 0006081081_201406 DEUTSCH...
Страница 133: ......