23 / 30
0006081265_201212
ENGLISH
0x55
●
ERROR_PARAMETERS SET STICK_CRC_DATA ? Parameters set stick faulty
...
Free
10.4 Application errors (starting from 0xA0)
0xA0
ERROR_STATUS DURATION_TOO_LONG (fan
and/or step motor error)
? in the 3, 16 and 23 statuses the fan and/or step motor cannot
reach their rated value within the foreseen time
? other status: internal error
0xA1
ERROR_FAN ACCELERATION (fan and/or step
motor error)
? in the 3, 16 and 23 statuses the fan and/or step motor cannot
reach their rated value within the foreseen time
? other status: internal error
0xA2
ERROR_SAFETY CHAIN_OPEN
? The safety chain has been opened or it is not closed
? The safety chain conductors are interrupted
0xA3
ERROR_PARAMETERS SET STICK_NO_
PASSWORD
? The MPA values differ from those of the parameters set stick.
The requested password has not been entered (time out).
0xA4
●
ERROR_V1_RESPONSE_WRONG
0xA5
●
ERROR_V2_RESPONSE_WRONG
0xA6
ERROR_ExTRANEOUS LIGHT
? Short-circuit to earth on the ionisation electrode
? The gas comes out and burns, for example by means of
close burners
0xA7
ERROR_NO_FLAME_DURING_SZA
? Ionisation electrode not properly set
? Ignition electrodes not properly set
? Insulation wires of the ignition electrodes or ionisation
electrode faulty
? Pneumatic unit not properly set / wrong gas type
? The gas valves do not open the gas passage
? Wrong set-up of the curve points
? The connected flame check (UV,...) detects light or it is faulty
? Network connection to the MPA reversed ("N" and "L1")
0xA8
ERROR_FLAME DISAPPEARANCE_DURING_
OPERATION
? Gas supply or pneumatic unit not set / not suitable for high
performances
? Faulty flame body
? The connected flame check (UV,...) does not detect any light
or it is faulty
0xA9
ERROR_FLAME DISAPPEARANCE_DURING_
STABILISATION TIME
? see 0xA8, but the problem occurs before.
0xAA
ERROR_LDW_INACTIVITY STATUS CHECK
? Faulty air pressure switch
? During the inactivity status check there is air pressure, for
example due to wind interference form the discharge gas
passage,...
? The air pressure switch threshold value is not properly set
0xAB
ERROR_NO_AIR PRESSURE
? the air pressure switch is not properly connected or it is faulty
? the fan does not turn
? the air pressure switch threshold value is not properly set
0xAC
●
ERROR_IGNITION_RESPONSE_WRONG
0xAD
ERROR_LACK OF GAS_GDWMIN
0xAE
ERROR_VPS_V1_NOT AIRTIGHT
0xAF
ERROR_VPS_V2_NOT AIRTIGHT
0xB0
●
ERROR_CIRCUIT ExTENSION TEST
...
Free
Содержание BPM 90 EVO
Страница 2: ......
Страница 27: ...27 30 0006081265_201212 ITALIANO SCHEMI ELETTRICI...
Страница 29: ...29 30 0006081265_201212 ITALIANO...
Страница 48: ...20 30 0006081265_201212 ENGLISH...
Страница 55: ...27 30 0006081265_201212 ENGLISH WIRING DIAGRAMS...
Страница 57: ...29 30 0006081265_201212 ENGLISH...
Страница 83: ...27 30 0006081265_201212 DEUTSCH SCHALTPLAN...
Страница 85: ...29 30 0006081265_201212 DEUTSCH...
Страница 111: ...27 30 0006081265_201212 P O L S K I SCHEMATY ELEKTRYCZNE...
Страница 113: ...29 30 0006081265_201212 P O L S K I...
Страница 115: ......