11 / 30
0006081265_201212
1
3
A
2
5
4
fig. 10
fig. 11
ENGLISH
GAS TRAIN DESCRIPTION FOR BPM 200 EVO / 300 EVO / 350 EVO GAS
PRESSURE ADJUSTMENT
1 - Gas solenoid valve
2 - Max. pressure adjustment
(clockwise to increase; anti-clockwise to decrease). Bring the
burner at the maximum output and adjust the gas valve so
that the flame appears as in fig.11.
3 - Min. pressure adjustment
(clockwise to increase; anti-clockwise to decrease). Bring
the burner at the minimum output and adjust the gas valve
so that the flame appears equally spread on the combustion
head, without any dark spot, looking like in fig.10.
NOTE: For min. pressure adjustment, remove cap A.
4 - 1" gas inlet
5 - Pressure plug
Maximum output flame
Minimum output flame