ENGLISH
37 / 42
0006160278_201804
MAINTENANCE TIME
COMBUSTION HEAD
ELECTRODES
VISUAL CHECK, CERAMIC INTEGRITY. END GRINDING, CHECK DISTANCE,
CHECK ELECTRICAL CONNECTION
YEARLY
FLAME DISC
INTEGRITY VISUAL CHECK FOR ANY DEFORMATIONS, CLEANING
YEARLY
IONISATION PROBE
VISUAL CHECK, CERAMIC INTEGRITY. END GRINDING, CHECK DISTANCE,
CHECK ELECTRICAL CONNECTION
YEARLY
COMBUSTION HEAD COMPONENTS
INTEGRITY VISUAL CHECK FOR ANY DEFORMATIONS, CLEANING
YEARLY
INSULATING GASKET
SEAL VISUAL INSPECTION AND POSSIBLE REPLACEMENT
YEARLY
GAS DELIVERY COUPLING SEAL
SEAL VISUAL INSPECTION AND POSSIBLE REPLACEMENT
YEARLY
AIR LINE
AIR GRILLE/DAMPERS
CLEANING
YEAR
AIR DAMPER BEARINGS
GREASING, (Note: apply only on burners with bearings requiring lubrication)
YEAR
FAN
FAN AND SCROLL CLEANING, DRIVE SHAFT GREASING
YEAR
AIR PRESSURE SWITCH
CLEANING
YEAR
AIR PRESSURE PORT AND PIPES
CLEANING
YEAR
SAFETY COMPONENTS
FLAME SENSOR
CLEANING
YEAR
GAS PRESSURE SWITCH
FUNCTIONAL INSPECTION
YEAR
VARIOUS COMPONENTS
ELECTRIC MOTORS
COOLING FAN CLEANING, BEARING NOISE CHECK
YEAR
MECHANICAL CAM
CHECK OF WEAR AND OPERATION, GREASING OF SLIDING BLOCK AND
SCREWS
YEAR
LEVERS/TIE-RODS/BALL JOINTS
CHECK OF ANY WEAR, COMPONENT LUBRICATION
YEAR
ELECTRICAL SYSTEM
CHECK OF CONNECTIONS AND TERMINAL TIGHTENING
YEAR
INVERTER
COOLING FAN CLEANING AND TERMINAL TIGHTENING
YEAR
CO PROBE
CLEANING AND CALIBRATION
YEAR
O2 PROBE
CLEANING AND CALIBRATION
YEAR
FUEL LINE
GAS FILTER
REPLACING THE FILTERING ELEMENT
YEAR
HYDRAULIC/GAS SEALS
CHECK OF ANY LEAKAGES
YEAR
COMBUSTION PARAMETERS
CO CONTROL
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
YEAR
CO2 CONTROL
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
YEAR
NOX CONTROL
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
YEAR
IONISATION CURRENT CONTROL
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
YEAR
SMOKE TEMPERATURE CONTROL
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
YEAR
GAS PRESSURE REGULATOR
PRESSURE MEASURED AT START-UP
YEAR
IMPORTANT
In case of heavy-duty operation or when using special fuels, the maintenance intervals must be reduced adapting them to the real
operating conditions, according to the indications of the maintenance technician.