ENGLISH
23 / 42
0006160278_201804
CAUTION / WARNINGS
This display is only shown in operating or stand-by mode.
DisplayLME71_008
Press “+” to display the flame signal amplifier.
The warning light flashes green.
The Display shows FL.1.
DisplayLME71_009
Press “+” (1...3seconds) to display the current flame signal.
The warning light flashes green.
Example: 11
DisplayLME71_010
By pressing “+” (>3 seconds), the dot after the digit starts flashing.
By releasing the push button, the value is displayed for two
minutes.
The warning light flashes green
Then the standard display appears.
Display: dot “.” flashes, value “11” no.
15.4.3 RESET
DisplayLME71_045
To reset the unit, press the “info” push button for 1... 3 seconds.
By releasing the push button, OFF is displayed.
Base unit is reset.
CAUTION / WARNINGS
For error meaning and diagnostic codification, see chapter ERROR CODE LIST.
Содержание BPM 90 E 50kW
Страница 2: ......
Страница 43: ...ENGLISH 41 42 0006160278_201804 WIRING DIAGRAMS...
Страница 45: ......