EQUIPMENT INSTALLATION
• Arrange the high voltage ignition cables separately, as far as possi-
ble from the equipment and other cables.
• Do not confuse live and neutral conductors.
• Install switches, fuses and grounding systems in accordance with
local regulations.
• The connection diagrams show the burner controls with neutral
grounded conductor.
• Make sure that the maximum permissible current of the connection
terminals is not exceeded.
• Make sure that the fairleads of the connected cables comply with the
applicable standards.
• Do not supply mains voltage to the equipment outlets. During the
testing of the devices controlled by the burner control (fuel valves,
etc.), the equipment must not be connected to the units.
• The mechanical coupling between the actuators and the fuel and air
control elements, or any other type, must be rigid.
• Check for the absence of short circuits on the air pressure switch
connection lines.
ELECTRICAL CONNECTION TO FLAME DETECTORS
IMPORTANT
The transmission of signals must be free from disturbances and
losses.
•
Always separate the flame detector cables from others
-
the capacitive reactance of the line reduces the size of the flame
signal;
- use a separate cable.
•
Adhere to the cable lengths of the flame detectors, which must not
exceed 30 m.
• The mains powered ionisation probe is not protected against electric
shock risks.
• Position the ignition electrode and the ionisation probe so that the
ignition spark cannot form an arc on the probe (risk of electrical over-
load) and cannot negatively affect the ionisation supervision.
OPERATION WITH LME INTERNAL CONTROL UNIT
DISPLAY AND PUSH BUTTON DESCRIPTION
DisplayLME71_001
DisplayLME71_001A
A
Push button A:
It displays the preset output
In lockout position: it displays the power value at the
moment of lockout
DisplayLME_001B
Info
Info and Enter push button
In case of fault, it resets and displays the fault cause
diagnostics
(see chapter FAULT CAUSE DIAGNOSTICS)
DisplayLME71_001C
_
Push button “-”
It displays the flame 2 signal current or the phases.
In lockout position: it displays the MMI phase at the
moment of the fault
DisplayLME71_001D
+
Push button “+”
It displays the flame 1 signal current or the phases.
In lockout position: it displays the MMI phase at the
moment of the fault.
DisplayLME71_001E
Three-colour warning LED
See chapter FLASHING CODE TABLE
DisplayLME71_001F
+
_
and
Push buttons “+”: Exit function
(press “+” and “-” simultaneously)
No selected value
A higher menu level
Press and hold for >1 second for backup/re-
store function
ENGLISH
24 / 40
0006160310_202001
Содержание BPM 10
Страница 2: ......
Страница 37: ...ITALIANO 35 40 0006160310_202001...
Страница 38: ...ITALIANO 36 40 0006160310_202001...
Страница 39: ...ITALIANO 37 40 0006160310_202001...
Страница 40: ...SCHEMI ELETTRICI ITALIANO 38 40 0006160310_202001...
Страница 42: ...ITALIANO 40 40 0006160310_202001...
Страница 77: ...ENGLISH 35 40 0006160310_202001...
Страница 78: ...ENGLISH 36 40 0006160310_202001...
Страница 79: ...ENGLISH 37 40 0006160310_202001...
Страница 80: ...WIRING DIAGRAMS ENGLISH 38 40 0006160310_202001...
Страница 82: ...ENGLISH 40 40 0006160310_202001...
Страница 83: ......