TROUBLESHOOTING
proBLem
poSSIBLe CaUSe
SoLUtIon
the equipment goes into “lock-out”
with the flame (red light on). fault in
the flame control device.
1) Disturbance to ionisation current from
ignition transformer.
2) Inefficient flame sensor (ionisation
probe).
3) Flame sensor (ionisation probe) position
incorrect.
4) Ionisation probe or relative earth cable.
5) Flame sensor electrical connection
cut-off.
6) Inefficient draught or fumes passage
blocked.
7) Flame disk or combustion heads dirty
or worn.
8) Equipment fault.
9) No ionisation.
1) Invert the ignition transformer power supply
(230V side) and check using an analogue
micro-ammeter.
2) Replace flame sensor
3) Correct the position of the flame sensor, and
then check its efficiency by connecting the
analogue micro-ammeter.
4) Check visually and using the instrument.
5) Restore the connection.
6) Ensure that the boiler fumes passage and
chimney connection are free.
7) Visually check and replace, if necessary.
8) Replace.
9) If the “earth” of the equipment is not efficient,
the ionisation current cannot be checked.
Check the efficiency of the “earth” at the
terminal concerned in the equipment and
at the “earth” connection of the electric
system.
the equipment goes into “lock-out”,
gas flows out, but there is no flame
(red light on).
fault in ignition circuit.
1) Fault in ignition circuit.
2) Ignition transformer cable discharges
to earth.
3) Ignition transformer cable disconnected.
4) Faulty ignition transformer.
5) The distance between electrode and
earth is incorrect.
6) Isolator dirty, therefore the electrode
discharges to earth
1) Check the ignition transformer power supply
(230V) and high voltage circuit (electrode
to earth or isolator broken under locking
terminal).
2) Replace.
3) Connect.
4) Replace.
5) Position at the correct distance
6) Clean or change the isolator or electrode.
the equipment goes into “lock-out”,
gas flows out, but there is no flame
(red light on)
1) Air/gas ratio incorrect.
2) Gas piping has not been properly bled of
air (in the case of first ignition).
3) The gas pressure is insufficient or
excessive.
4) Air passage between disk and head too
narrow.
1) Correct the air/gas ratio (there is probably too
much air or very little gas)
2) Bleed the gas pipe again, taking great care.
3) Check the gas pressure value at the time
of ignition (use a water pressure gauge,
if possible).
4) Adjust the disk/head opening.
Содержание BGN 250 DSPGN ME
Страница 2: ......
Страница 25: ...23 26 0006081538_201308 ITALIANO SCHEMA ELETTRICO EVENTUALE COLLEGAMENTO A MODULAZIONE ESTERNA...
Страница 26: ...24 26 0006081538_201308 ITALIANO START PER REGISTRATORE CORRENTE MINIMA DI OIONIZZAZIONE 1 4 A...
Страница 51: ...23 26 0006081538_201308 ENGLISH WIRING DIAGRAM POSSIBLE CONNECTION TO EXTERNAL MODULATION...
Страница 52: ...24 26 0006081538_201308 ENGLISH START FOR RECORDER MINIMUM IONISATION CURRENT 1 4 A...
Страница 55: ......