background image

16 / 36 

0006081062_200

904

E

N

G

L

I

S

H

 Control box or 

programmer

Safety time

s

Preventila

-

tion time

s

Pre-

ignition

s

Post-

ignition

s

Time betwe

-

en opening of 

pilot valves and 

opening of main 

valves

s

Cut out of pilot 

flame after opening 

of main valves

s

Time between ope

-

ning1st flame valve 

and 2nd flame 

valve

s

  LFL 1.333

3

31,5

6

3

12

3

12

DESCRIPTION OF WORKING

Closing switch 1, if the thermostats are closed, the voltage reaches 
the command and control equipment (switching on of LED 2) which 
starts it working. The fan motor is thus switched on (LED 3) to carry 
out the preventilation of the combustion chamber, at the same time 
the air damper control servo motor moves to the opening position 
corresponding to the maximum regulated power.
At  the  end  of  the  preventilation  stage  the  air  damper  has  to  be 
returned to the ignition flame position. If the pressure control switch 
for the ventilation air detects sufficient pressure, the ignition tran

-

sformer goes on  (LED 4) and, after two seconds, the main gas and 
safety valves open (LED 5)
Note that:

a)  The main valve has a device for the proportional adjustment of 

the air to gas ratio.

b)  The safety valve is an ON/OFF type.

c)  The  air  damper  is  activated  by  an  electric  servo  motor  (see 

0002933220 to 200Lx at 390Lx and 0002933490 for 540Lx)

, re-

member  that when the burner is stopped by 

  the thermostat, the gate damper 
  is brought back by the servo motor to its closed position.

!

The gas supply at the ignition flame position must ge

-

nerally be greater than the minimum modulation capa

-

city. The ignition flame position can be adjusted with 
the air damper control servo motor. (see 

0002933220

to 200Lx at 390Lx and 0002933490 for 540Lx).

The  presence  of  the  flame,  detected  by  the  control  device 
itself,  permits  the  continuance  and  completion  of  the  igni

-

tion  stage  with  the  switching  off  of  the  ignition  transformer. 
Subsequently  the  servo  motor  progressively  opens  the  air 
damper  and  the  pneumatic  valve  allows  the  gas  supply  to 
increase to its set maximum.
If there is no flame, the control box stops in its “safety lock-
out” (LED 7) within 3 seconds from the opening of the main 
valve. In the case of safety lock-out the valves immediately 
close again. To release the control box from its safety posi

-

tion press button 8 on the display panel.

DESCRIPTION OF MODULATION WORKING

When  the  burner  is  running  at  minimum  capacity,  if  the  modula

-

tion probe allows,  (adjusted to a temperature or pressure value 
greater  than  that  in  the  boiler)  the  air  adjustment  servo  motor 
starts  to  turn  causing  gradual  increase  in  combustion  air  sup

-

ply  and,  consequently  also  of    gas,  up  to  the  maximum  supply 
for  which  the  burner  has  been  set.  The  increase  in  the  fan  air 
pressure is detected by the proportional gas valve sensor which 
gradually  adjusts  gas  supply  to  the  change  in  air  pressure. 

The  burner  stays  at  maximum  delivery  until  the  temperature  or 
pressure reaches a level high enough to cause the modulation pro

-

be to turn the air adjustment servo motor in the opposite direction.
The  backward  rotation  and  consequent  reduction  in  gas  and  air 
supply  happens  at  brief  time  intervals.  With  this  manoeuvre  the 
modulation system seeks to balance the quantity of heat supplied 
to the boiler with that which the boiler itself provides. The modu

-

lation probe applied to the boiler detects changes in demand and 
automatically  adjusts  the  supply  of  fuel  and  of  combustion  air, 
switching on the servo motor with an increased or decreased rota

-

tion. If, even with fuel supply at minimum, the limit value is reached 
(temperature or pressure) for which the device is set for complete 
stop, (through thermostat or pressure switch) the burner is stopped 
by the device.
By lowering the temperature or pressure again below the burner 
stop device-triggering figure it is switched on again in accordance 
with the program described in the previous paragraph.

1

2

3

4

6

8

7

5

1  Main ON-OFF switch

2  Live voltage light

3  Fan working light

4  Transformer on light

5  Gas valves working indicator light

6  Safety fuses

7 Control box lock-out light

8 Control box release button

Содержание BGN 200 LX

Страница 1: ...ale istallazione impiego manutenzione BGN 200 LX LX V BGN 300 LX LX V BGN 390 LX LX V BGN 540 LX LX V Maintenance use and installation manual Manual de mantenimiento uso e instalaci n Manuel d install...

Страница 2: ......

Страница 3: ...ommencer utilise le br leur lire attentivement les recommandations de la notice RECOMMANDATIONS A L ATTENTION DE L UTILISATEUR POUR UN USAGE DU BRULEUR EN TOUTE SECURITE jointe au manuel d in structio...

Страница 4: ...0006081062_200904...

Страница 5: ...correggere se necessario il rapporto tarato agendo sulla vite V fino a quando il valore misurato ottimale NOTA Per diminuire la quantit di aria rispetto al gas e quindi per aumentare la percentuale d...

Страница 6: ...ion atmosfere V min mini max maxi N 1 mbar pL max maxi 100 mbar V max maxi 3 1 pF max maxi 5 mbar pBr max maxi 100 mbar pL min mini 0 4 mbar pBr min mini 0 5 mbar pF min mini 2 mbar V min mini 0 75 1...

Страница 7: ...e 9 Sostituirla 10 Se la massa dell apparecchiatura non efficiente non si verifica la corrente di ionizzazione Verificare l efficienza della massa all apposito morsetto della apparecchiatura e al coll...

Страница 8: ...36 36 0006081062_200904 I T A L I A N O...

Страница 9: ...eclare under our own responsibility that our CE marked products Series Sparkgas BTG BGN Minicomist Comist RiNOx BT BTL GI GI Mist PYR TS TBG Description domestic and industrial blown air burners fired...

Страница 10: ...r or if the owner moves and leaves the equipment make sure that the booklet always goes with the equipment so it can be consulted by the new owner and or installer For all equipment with optionals or...

Страница 11: ...rent law and regulations since incorrect installation may cause damage to person animals or things for which damage the manufacturer shall not can be held responsible Before installation it is advisab...

Страница 12: ...N 4 M12 N 4 M20 N 4 M20 N 6 M20 EXAGONAL NUTS N 4 M12 N 4 M20 N 4 M20 N 6 M20 FLAT WASHERS N 4 M12 N 4 M20 N 4 M20 N 6 20 BGN 200 LX V BGN 300 LX V BGN 390 LX V BGN 540 LX V THERMIC CAPACITY MAX kW 21...

Страница 13: ...Control box MOD A A1 A2 B1 B5 C D MIN D MAX E F BGN 200 LX 835 400 435 580 150 1630 280 480 300 220 BGN 300 LX 880 400 480 580 177 1630 280 480 316 275 BGN 390 LX 880 400 480 580 177 1630 280 480 316...

Страница 14: ...regulation servomotor 5 Hinge 6 Combustion head air control knob 7 Fan motor 8 Air pressure switch 9 Control box MOD A A1 A2 B1 B5 C D MIN D MAX E F BGN 540 LX 1155 470 685 695 283 2110 330 600 400 35...

Страница 15: ...V 10 1 Frequency converter BGN 300 390 LX V MOD A A1 A2 B1 B5 C D MIN D MAX E F BGN 200 LX V 835 400 435 580 150 1630 280 480 300 220 BGN 300 LX V 880 400 480 580 177 1870 280 480 316 275 BGN 390 LX...

Страница 16: ...rvomotor 5 Hinge 6 Combustion head air control knob 7 Fan motor 8 Air pressure switch 9 Control box 10 Frequency converter MOD A A1 A2 B1 B5 C D MIN D MAX E F BGN 540 LX V 1155 470 685 695 283 2165 33...

Страница 17: ...3 5 7 9 11 13 15 Campo di lavoro Operating field Arbeitsfeld BGN 200 LX X 8 40 mm Potenzialit Power Kapazit t kW Position of air diffusor X min left and X max right BGN 200LX Operating field BGN 200LX...

Страница 18: ...7 Campo di lavoro Operating field Arbeitsfeld BGN 300 LX X 10 40 mm Potenzialit Power Kapazit t kW Position of air diffusor X min left and X max right BGN 300LX Operating field BGN 300LX X 10 40mm Kw...

Страница 19: ...9 11 13 15 17 Operating field BGN 390 LX X 10 40 mm PFeu power kW pFR combustion pressure mbar Position of air diffusor X min left and X max right BGN 390LX Operating field BGN 300LX X 10 40mm Kw Pow...

Страница 20: ...TING FIELD i The working fields are obtained from test boilers corresponding to the standard EN676 and are indicatively for the combination burner boiler For correct working of the burner the size of...

Страница 21: ...adjusted while working at the maximum capacity actually used by the burner The delivery pressure must be adjusted to a figure slightly lower than the maximum obtainable that which is obtained when the...

Страница 22: ...ion chamber Burner flange Pressure detection pipe connection nipple in combustion chamber Pressure take off in combustion chambe CHAMBER FOR MODEL BGN 540 LX FOR MODELS BGN 200 LX BGN390 LX N 00029349...

Страница 23: ...3 Turn the cam 6 so that the float exerts sufficient pressure on the two cables then tighten the screws that fasten the cable float Finally connect the two 7 and 4 pole plugs the housings for the cabl...

Страница 24: ...tic valve allows the gas supply to increase to its set maximum If there is no flame the control box stops in its safety lock out LED 7 within 3 seconds from the opening of the main valve In the case o...

Страница 25: ...VEF DMV VEF set the desired value see the specific instruc tions for the gas valve MB VEF DMV VEF in the following pages 9 With the burner panel switch set to 0 and main circuit breaker on manually tu...

Страница 26: ...singthecontact anormallyopencontact when air pressure in the burner reach a sufficient value Note that if the normally open contact does not close insufficient air pressure thecontrolboxperformsitscyc...

Страница 27: ...regulation as explained above When the maximum desired output is reached correct the position of the device closing the air on the combustion head by moving it forwards or backwards so as to have a s...

Страница 28: ...CT ADJUSTMENT Burner s head adjusting and xing knob Combustion air inlet Gate sensibly open MAINTENANCE The burner does not need special maintenance However it is advis able to check that the gas lter...

Страница 29: ...iagram relative to the speci c burner model NOTE if the distance X is reduced the NOx emissions value falls Always adjust the distance X between the minimum and maximum valuesspeci ed in the work eld...

Страница 30: ...22 36 0006081062_200904 E N G L I S H...

Страница 31: ...23 36 0006081062_200904 E N G L I S H CAMS REGULATION SERVONMOTOR SQM 10 20 FOR BGN LX N 0002933490...

Страница 32: ...nd of the tolerated post combustion period The tests will end only at the end of the pre ventilation time of the next start up The validity of working of the ame control circuit is checked each time t...

Страница 33: ...mutation contact for air damper MIN position M Motor fan or burner NTC NTC resistor QRA UV probe R Thermostat or pressure probe RV Fuel valve with continuous regulation S Fuse SA Air damper servomotor...

Страница 34: ...inal 19 12 t5 Time between end of t4 and consensus at power regu lator or at valve on terminal 20 18 t6 Post ventilation time with M2 3 t7 Time between consensus for start up and voltage at terminal 7...

Страница 35: ...ltration of condensate into the command and control equipment Electromagnetic discharges must be checked on the applica tion plan Control program in the event of stopping indicating position of stop A...

Страница 36: ...or pL blower pressure 9 Setting screw ratio V 10 Test point connection G 1 8 down stream of filter possible of both sides 11 Test point connection M4 down stream of V2 12 Setting screw zero point adju...

Страница 37: ...29 36 0006081062_200904 E N G L I S H Pe Gas inlet pressure...

Страница 38: ...30 36 0006081062_200904 E N G L I S H DUNGS mod DMV VEF 5065 11 5125 11 N 0006080717 Rev 2002 06 INSTRUCTIONS FOR DOUBLE SOLENOID VALVE GAS AIR RATIO CONTROL...

Страница 39: ...31 36 0006081062_200904 E N G L I S H...

Страница 40: ...N hacia los valores negativos Ponga el quemador al m ximo de la modula ci n mida el contenido de CO2 o O2 y CO en los humos y si fuera necesario ajuste la relaci n tarada con el tornillo V hasta que...

Страница 41: ...pBr max maxi 100 mbar pL min mini 0 4 mbar pBr min mini 0 5 mbar pF min mini 2 mbar V min mini 0 75 1 V pBr pL MB VEF Einstellbereich Setting range Plange de r glage Campo di regolazione Correcci n pu...

Страница 42: ...os 8 Limpiar 9 Sustituirlo 10 Si la puesta a tierra del quemador no funciona la corriente de ionizaci n no se efect a Controlar la puesta a tierra del borne del aparato y del sistema el ctrico Llama a...

Страница 43: ...36 36 0006081062_200904 E S P A O L...

Страница 44: ...149 162 0006081062_200904...

Страница 45: ...150 162 0006081062_200904...

Страница 46: ...151 162 0006081062_200904...

Страница 47: ...152 162 0006081062_200904...

Страница 48: ...153 162 0006081062_200904...

Страница 49: ...154 162 0006081062_200904...

Страница 50: ...155 162 0006081062_200904...

Страница 51: ...156 162 0006081062_200904...

Страница 52: ...157 162 0006081062_200904...

Страница 53: ...158 162 0006081062_200904...

Отзывы: