SPECIFICATIONS FOR PROPANE USE
•
Operating costs approximate assessment;
-
1 m3 of liquid gas in gaseous stage has a lower heating capaci
-
ty, of nearly 25.6 kWh.
-
To obtain 1 cu.m of gas, about 2 kg of liquid gas are needed, i.e.
about 4 litres of liquid gas.
• Safety provisions
•
Liquid propane gas (L.P.G.) in the gaseous form has a greater
specific weight than air (specific weight relative to air = 1.56 for
propane), which means it does not disperse in air like natural
gas, which has a lower specific weight than air (specific weight of
natural gas relative to air = 0.60), but precipitates and spreads out
at ground level (as if it were a liquid). Summing up the concepts
we deem most relevant fir the use of LPG
•
Liquefied petroleum gas (L.P.G.) burners and/or boilers may be
used only in premises located above ground level and certified
toward free spaces. Installations using liquid gas are not allowed
in underground or semi-underground premises.
•
Rooms where liquid gas is used must have ventilation inlets
without closing devices, located on external walls, in compliance
with the local exiting rules.
•
Carrying out the propane gas system to ensure
correct, safe operation.
Natural gasification from sets of cylinders or a tank can be used only
in low power systems. Gas supply capacity on the basis of tank size
and minimum outdoor temperature are shown in the table below, as an
approximate indication only.
DANGER / ATTENTION
The maximum and minimum power (kW) of the burner refers
to natural gas which is more or less the same as with propane.
•
Combustion control
To keep consumption down and mainly to prevent serious problems,
regulate the combustion using the specific instruments. It is absolutely
essential to check that the percentage of carbon monoxide (CO) does not
exceed the maximum permitted value by the local existing regulation (use
a combustion analyser or other similar instrument).
DANGER / ATTENTION
The warranty does not cover burners burning liquid gas (L.P.G.)
in installations in which these measures have not been taken.
Minimum
temperature
- 15 °C
- 10 °C
- 5 °C
- 0 °C
+ 5 °C
Tank 990 l.
1.6 Kg/h
2.5 Kg/h
3.5 Kg/h
8 Kg/h
10 Kg/h
Tank 3000 l.
2.5 Kg/h
4.5 Kg/h
6.5 Kg/h
9 Kg/h
12 Kg/h
Tank 5000 l.
4 Kg/h
6.5 Kg/h 11.5 Kg/h
16 Kg/h
21 Kg/h
28 / 46
0006160357_202305
ENGLISH
Содержание 56760010
Страница 2: ......
Страница 38: ...SCHEMI ELETTRICI TBML 450 ME 510 ME BT 335 36 46 0006160357_202305 ITALIANO ...
Страница 39: ...TBML 450 ME 510 ME BT 335 37 46 0006160357_202305 ITALIANO ...
Страница 40: ...TBML 450 ME 510 ME BT 335 38 46 0006160357_202305 ITALIANO ...
Страница 41: ...TBML 450 ME 510 ME BT 335 39 46 0006160357_202305 ITALIANO ...
Страница 42: ...TBML 450 ME 510 ME BT 335 I1 I2 BA I4 I3 40 46 0006160357_202305 ITALIANO ...
Страница 43: ...TBML 650 ME 750 ME BT 335 41 46 0006160357_202305 ITALIANO ...
Страница 44: ...TBML 650 ME 750 ME BT 335 42 46 0006160357_202305 ITALIANO ...
Страница 45: ...TBML 650 ME 750 ME BT 335 43 46 0006160357_202305 ITALIANO ...
Страница 46: ...TBML 650 ME 750 ME BT 335 44 46 0006160357_202305 ITALIANO ...
Страница 47: ...TBML 650 ME 750 ME BT 335 I1 I2 BA I4 I3 45 46 0006160357_202305 ITALIANO ...
Страница 84: ...WIRING DIAGRAMS TBML 450 ME 510 ME BT 335 36 46 0006160357_202305 ENGLISH ...
Страница 85: ...TBML 450 ME 510 ME BT 335 37 46 0006160357_202305 ENGLISH ...
Страница 86: ...TBML 450 ME 510 ME BT 335 38 46 0006160357_202305 ENGLISH ...
Страница 87: ...TBML 450 ME 510 ME BT 335 39 46 0006160357_202305 ENGLISH ...
Страница 88: ...TBML 450 ME 510 ME BT 335 I1 I2 BA I4 I3 40 46 0006160357_202305 ENGLISH ...
Страница 89: ...TBML 650 ME 750 ME BT 335 41 46 0006160357_202305 ENGLISH ...
Страница 90: ...TBML 650 ME 750 ME BT 335 42 46 0006160357_202305 ENGLISH ...
Страница 91: ...TBML 650 ME 750 ME BT 335 43 46 0006160357_202305 ENGLISH ...
Страница 92: ...TBML 650 ME 750 ME BT 335 44 46 0006160357_202305 ENGLISH ...
Страница 93: ...TBML 650 ME 750 ME BT 335 I1 I2 BA I4 I3 45 46 0006160357_202305 ENGLISH ...
Страница 95: ......