Using good quality water (see section "About water care" on page 21),fill the tank following the steps outlined
below. For proper, long-term operation of the thermal storage unit, the tank must be filled exactly to the prescribed
level.
1. Remove the access cover on the top of the unit. Use a fill hose to fill the tank. See following table “Fluid
volumes” for the approximate volume of water required.
Model
Tank volume
(liters of water)
Coil volume
(liters of glycol solution)
TSU-237M
11320
985
TSU-476M
22110
1875
TSU-594M
28250
2320
TSU-761M
34640
2990
TSU-L184M
8820
770
TSU-L370M
17250
1460
TSU-L462M
22030
1810
TSU-L592M
27020
2280
Fluid volumes
2. Continue filling the tank until the water level in the clear sight tube reaches the "0% ice build" level (See figure
“Water level in sight tube”.
CAUTION
For proper operation tank must be initially filled to the “0” ice build level.
W W W . B A L T I M O R E A I R C O I L . E U
26