Rotate the black button to dial 7 and press to confirm. The display indicates 'Range successfully changed'. In
case the button is pressed without dialing 7 you return to the previous menu and values are not stored.
After the range is entered, the following screen appears for a few seconds, followed by the next screen:
Now follow the procedure to set the zero level. When pressing the black button you enter the screen below. Rotate
the black button to select 'Set Zero Level' and press to activate. Make sure you only do this when no ice is present
in the ice tank and when the water level is at the zero level of the sight glass. (For concrete tank applications make
sure the water level is just above the coil header.)
Select 'Set Zero Level' by rotating the black button and press to confirm.
Rotate the black know to change 'No' to 'Yes' and press to confirm your choice. When choosing 'No', you return to
the previous menu. When pressing 'Yes' you access the screen below: