FXV3/CXVT Rigging & Assembly Instructions
–
Unit Rigging & Assembly
Page | 22
Plain Pipe Stub Coil Connections Nitrogen Charge Removal
Coils may be supplied with plain pipe stub coil connections that are capped and charged with nitrogen from the factory.
for information on validating coil charge pressure. Plain pipe stub coil connections must be field cut
and beveled before welding. Prior to cutting the pipe stub, relieve the pressure inside each coil using the factory
installed Schrader valve.
Figure 27. Coil Connections Capped and Charged