background image

8

If belt tensioning is required, proceed as follows:

1. Loosen the lock nut on the Motor Base Adjusting
Screw (see Figure 4 & 5).

2. Turn the Motor Base Adjusting Screw clockwise to
tension the belt, or counterclockwise to relieve belt
tension. During adjustment of belt tension, the drives
should be rotated several times by hand to evenly
distribute the tension throughout the belt.

3. When the belt is properly tensioned, retighten the
locking nut on the Motor Base Adjusting Screw.

NOTE: There should be no “chirp” or “squeal” when the
fan motor is started.

The drive alignment should be checked annually to
ensure maximum belt life. 
This can be done by placing
a straight edge across the driver and driven sheaves as
shown in Figure 7a for standard drives and in Figure 7b
for ENERGY-MISER

®

Fan System drives. When the drives

are properly aligned, the straight edge will contact all four
points as indicated. There should be no more than 1/16"
deviation from four point contact. If realignment is neces-
sary, loosen the motor sheave and align it with the fan
sheave. Allow approximately 1/4" for draw-up as the
bushing screw is retightened.

Figure 6b

Figure 7a — Standard Drives

Figure 7b — ENERGY-MISER

®

Fan System Drives

Corrosion Protection

The Series 3000 and Series 1500 Cooling Towers are con-
structed of corrosion-resistant materials. The wet deck sur-
face is made of an inert synthetic material, which requires
no protection against rot, decay, rust or biological attack.
Other materials used in construction of the equipment,
which are listed below, should be inspected regularly.

Galvanized steel components
Galvanized steel components should be inspected for
blemishes or corrosion. Affected areas should be wire
brushed and recoated with a cold galvanizing compound
such as ZRC.

BALTIBOND

®

Corrosion Protection System

Components

Galvanized steel components protected with the
BALTIBOND

®

Corrosion Protection System may develop

scratches, scrapes or blemishes. These may be touched
up with a repair kit (B.A.C. Part No. 16-133P). In the
unlikely event that the damage is more extensive than
simple scratches or minor blemishes, contact your local
B.A.C. Representative.

Stainless Steel Components

Stainless steel components should be inspected for signs
of blemishes or corrosion and cleaned with stainless steel
wool as necessary. If more extensive corrosion is preva-
lent, contact your local B.A.C. Representative.

Fiberglass Re-Inforced Polyester (FRP) Components

Series 3000 and Series 1500 Cooling Towers are provided
with FRP casing panels and air inlet louvers as standard.
These components should be inspected for accumulation
of dirt and cleaned with soap and water as necessary.

Содержание 3000 Series

Страница 1: ...ntenance be developed and carried out This bulletin is published as a guide to establishing such a program Included in the bulletin are the recommended services for start up operation and shutdown and...

Страница 2: ...tent of impurities in the air and water determines the frequency of most maintenance services and also governs the extent of water treatment which can vary from a simple continuous bleed and biologica...

Страница 3: ...r property damage All electrical mechanical and rotating machinery constitute a potential hazard particularly for those not familiar with the design construction and operation Accordingly adequate saf...

Страница 4: ...to obtain even water distribution 13 Open the valve in the tower bleed line by others and adjust bleed to the recommended rate See Water Treatment page 10 continued 14 Check the voltage and current o...

Страница 5: ...ically purge the EASY CLEAN Chamber of dirt and debris collected by the strainer The strainer should be cleaned periodically as shown in the Recommended Maintenance Schedule This is accomplished by un...

Страница 6: ...f the thermal load is less than the design load at the time of unit start up the procedure may produce operating levels greater than that shown It may be necessary to re adjust the float in order to a...

Страница 7: ...uch as one of those recommended for lubricating the fan shaft bearings BALTIDRIVE POWER TRAIN The BALTIDRIVE Power Train consists of a specially designed belt with corrosion resistant fan motor sheave...

Страница 8: ...ies 3000 and Series 1500 Cooling Towers are con structed of corrosion resistant materials The wet deck sur face is made of an inert synthetic material which requires no protection against rot decay ru...

Страница 9: ...eration CAUTION The plug must be reinstalled during warm weather to obtain full thermal performance When the cooling tower is operated at wet bulb tempera tures below freezing ice may form on wetted a...

Страница 10: ...M per 100 tons of refrigeration Evaporation Rate Water Flow Rate x Range x 001 Example At a flow rate of 900 GPM and a cooling range of 10 F the evaporation rate is 9 GPM 900 GPM x 10 F x 001 9 GPM If...

Страница 11: ...culating pump They should not be batch fed directly into the cold water basin 3 Acid water treatment is not recommended unless the unit s have been furnished with the BALTIBOND Corrosion Protection Sy...

Страница 12: ...ment quality Local assistance with service problems The following is a list of retrofit options and accessories to further simplify maintenance access Internal Service Platform Ladder with Handrails E...

Отзывы: