background image

6

Maintenance

Procedures

Quarterly, or more often if necessary, the entire cold-
water basin should be drained, cleaned, and flushed with
fresh water to remove the silt and sediment which
normally collects in the basin.

It is important to note that although stainless steel and
BALTIBOND

®

Corrosion Protection System — protected

basins provide added protection from corrosion, the
same maintenance applies to them as well.

If not removed periodically, this sediment can become
corrosive and cause deterioration of the protective finish
of metallic basins. When flushing the basin, the strainers
should be left in place to prevent the sediment from re-
entering the tower system. After the basin has been
flushed, the strainers should be removed, cleaned, and
replaced before refilling the basin with fresh water.

WARNING: Openings and/or submerged obstructions
may exist in the bottom of the cold-water basin. Use
caution when walking inside this equipment.

MAKE-UP VALVE:
A float operated mechanical water make-up assembly is
furnished as standard equipment on the cooling tower
(unless the unit has been ordered with the optional
electric water level control package or for remote sump
application). It is located inside the unit cold water basin
within easy reach from the access door at the connection
end of the unit on the Series 3000 and Series 1500
Cooling Towers.

The standard make-up assembly consists of a bronze
make-up valve connected to a float arm assembly and
actuated by a large diameter polystyrene filled plastic
float. The float is mounted on an all-thread rod which is
held in place by wing nuts. The operating water level in
the cold water basin can be adjusted by repositioning the
float and all-thread rod using the wing nuts provided.

The make-up assembly should be inspected monthly
and adjusted as necessary. The valve itself should be
inspected annually for leakage and the valve seat
replaced if necessary. The make-up water supply
pressure should be maintained between 15 and 50
psig for proper operation of the valve.

To set the initial basin water level, adjust the wing nuts so
that the make-up valve is completely closed when the
water level in the cold water basin is 1/2" below the
overflow connection. Under design thermal load and with
average city water pressure (15 to 50 psig) at the valve,
this setting should produce the operating water levels
stated in Table 2. Note that if the thermal load is less than
the design load at the time of unit start-up, the procedure
may produce operating levels greater than that shown. It
may be necessary to re-adjust the float in order to attain

the recommended operating level. The unit basin should
be closely monitored and water level adjusted as
necessary during the first 24 hours of operation.

As an option, an electric water level control package is
available in lieu of the above described mechanical
make-up assembly. The package consists of a probe-
type liquid level control assembly and a slow-closing
solenoid valve. Stainless steel electrodes, factory-set at
predetermined lengths, extend from an electrode holder
into the cold-water basin. These electrodes should be
periodically cleaned to prevent accumulations of
scale, corrosion, sludge or biological growth from
interfering with the electrical circuit. 
With the electric
water level control package, the water level is maintained
at the recommended operating level regardless of the
system thermal load. Therefore, it is not necessary, nor is
it recommended that the operating level be adjusted.

During the start-up of units equipped with the electric
water level control package, the control unit should be
bypassed in order to fill the unit 1/2" below the overflow
connection.

Operation at the recommended water level will ensure
that the unit basin contains sufficient water volume to
prevent air entrainment in the circulating pump during
system start-up and to provide sufficient excess basin
capacity to accept the total system pull-down volume.

(“Pull-down volume” is defined as that quantity of water
suspended in the tower during pump operation plus that
contained in the water distribution system, external piping,
and any heat exchangers which could drain to the tower
cold water basin when the circulating pump is shut down.)

FAN MOTOR:
The standard fan motor used on Series 3000 and Series
1500 Cooling Towers is a T.E.A.O. motor (Totally
Enclosed, Air Over) with permanently lubricated ball
bearings and special moisture protection on the bearings,
shaft, and windings. The only servicing required during
operation is to clean the outside surface of the motor at
least quarterly to insure proper motor cooling. Additionally,
after prolonged shutdowns, the motor insulation be
checked with a “megger” insulation tester prior to
restarting the motor.

(continued)

(continued)

Height of Water in

Model No.

the Cold Water Basin

(in.)

Series 3000 Models

33245 to 33501

8

3

4

"

Series 3000 Models

33522 to 331328

9

3

4

"

All Series 1500 Models

8

3

4

"

TABLE 2. Cold Water Basin Operating Water Level

Содержание 3000 Series

Страница 1: ...ntenance be developed and carried out This bulletin is published as a guide to establishing such a program Included in the bulletin are the recommended services for start up operation and shutdown and...

Страница 2: ...tent of impurities in the air and water determines the frequency of most maintenance services and also governs the extent of water treatment which can vary from a simple continuous bleed and biologica...

Страница 3: ...r property damage All electrical mechanical and rotating machinery constitute a potential hazard particularly for those not familiar with the design construction and operation Accordingly adequate saf...

Страница 4: ...to obtain even water distribution 13 Open the valve in the tower bleed line by others and adjust bleed to the recommended rate See Water Treatment page 10 continued 14 Check the voltage and current o...

Страница 5: ...ically purge the EASY CLEAN Chamber of dirt and debris collected by the strainer The strainer should be cleaned periodically as shown in the Recommended Maintenance Schedule This is accomplished by un...

Страница 6: ...f the thermal load is less than the design load at the time of unit start up the procedure may produce operating levels greater than that shown It may be necessary to re adjust the float in order to a...

Страница 7: ...uch as one of those recommended for lubricating the fan shaft bearings BALTIDRIVE POWER TRAIN The BALTIDRIVE Power Train consists of a specially designed belt with corrosion resistant fan motor sheave...

Страница 8: ...ies 3000 and Series 1500 Cooling Towers are con structed of corrosion resistant materials The wet deck sur face is made of an inert synthetic material which requires no protection against rot decay ru...

Страница 9: ...eration CAUTION The plug must be reinstalled during warm weather to obtain full thermal performance When the cooling tower is operated at wet bulb tempera tures below freezing ice may form on wetted a...

Страница 10: ...M per 100 tons of refrigeration Evaporation Rate Water Flow Rate x Range x 001 Example At a flow rate of 900 GPM and a cooling range of 10 F the evaporation rate is 9 GPM 900 GPM x 10 F x 001 9 GPM If...

Страница 11: ...culating pump They should not be batch fed directly into the cold water basin 3 Acid water treatment is not recommended unless the unit s have been furnished with the BALTIBOND Corrosion Protection Sy...

Страница 12: ...ment quality Local assistance with service problems The following is a list of retrofit options and accessories to further simplify maintenance access Internal Service Platform Ladder with Handrails E...

Отзывы: