BVS Cockpit
Validation type
Whether a connected IO-Link device receives access to the IO-Link master can be controlled using validation.
Configuration options:
Description
0
No validation
1
Allows communication to the IO-Link master only for devices whose vendor ID (VID)
and device ID (DID) correspond to the configured values.
2
Identical to 1, in addition the serial number of the IO-Link device is checked.
Vendor ID, VID
Vendor ID for the IO-Link device (refer to the manual for the device)
Device ID, DID
Device ID for the IO-Link device (refer to the manual for the device)
Serial Number
(SerNum), optional
Serial number for the IO-Link device (if available; refer to the IO-Link device's type
plate)
Parameter Server
Description
Switched
on
Data management functions enabled, parameter data and identification data of the IO-Link device
are stored permanently.
Switched
off
Data management functions disabled, stored parameter data and identification data of the IO-Link
device remain stored.
Delete
Data management functions disabled, stored parameter data and identification data of the IO-Link
device remain stored.
Enable up-
load
If only the upload is enabled, the master always starts an upload of the parameter data. In this case,
the upload is independent of the upload flag of the IO-Link device. If there are no data stored in the
master port, an upload also takes place (e.g. after deleting the data or before the first data upload).
Enable
download
If only the download is enabled, the master always starts a download of the parameter data. In this
case, the download is likewise independent of the upload flag of the IO-Link device. If there are no
data stored in the master port, first an upload takes place (e.g. after deleting the data or before the
first data upload).
Enable up-
load
and down-
load
If upload and download are enabled, different parameter sets are distinguished depending on the up-
load flag of the IO-Link device. If there are no parameter data stored in the IO-Link master port, a
first upload also takes place (e.g. after deleting the data or before the first data upload).
If the upload flag is set on the IO-Link device, an upload of the parameter data takes place.
If no upload flag is set and parameter data has already been stored, a download of the parameter
data always takes place.
Содержание BVS SC-C1280Z00-30-000
Страница 1: ...BVS SC _1280Z00 30 0 0 SMARTCAMERA Fieldbus...
Страница 2: ......
Страница 5: ...www balluff com 5 BVS Cockpit User s manual...
Страница 43: ...www balluff com 43 BVS Cockpit Determining the station name 1 Define the PROFINET station name of the device...
Страница 53: ...www balluff com 53 BVS Cockpit 3 Select SMARTCAMERA Module BVS_SC 1280 and apply to the configuration...