BSP B/M/V _ _ _ - _ _ _ _ _ - _ _ _ S1A - S4(- _ _ _ )
Trasmettitori di pressione IO-Link
Dati parametrici
I dati parametrici del sensore di pressione corrispondono al profilo Smart Sensor.
Index
hex
Subindex
hex
Object name
Single Value
Default
Commento
0x02
0x00
System Commands
0x81 = cancellare valore min./max
0x82 = res
0xA0 = Set0
L’azione viene
eseguita mediante
scrittura nel
subindex.
0x03
0x00
Data Storage Index
0x01: Upload Start
0x02: Upload End
0x03: Download Start
0x04: Download End
0x05: Datastorage Break
0x0C
0x00
Device Access Lock 0x00: Unlocked
0x01: IO-Link Lock
0x02: Datastorage Lock
0x03: IO-Link Lock + Datastorage Lock
0x00:
Unlocked
0x24
0x00
Device status
0x00 Device is operating properly
0x02 Out-of-Specification
0x04 Failure
0x3D
0x02
SwitchPoint mode
0x80: Hysteresis NO
0x81: Hysteresis NC
0x82: Window NO
0x83: Window NC
0x80: HNo
Index
hex
Subindex
hex
Object name
Access
Length
Value Range
Gradient Unit Default
0x3C
0x01
SetPoint 1 = SP1
R/W
2 byte
Process Data
100%
0x3C
0x02
SetPoint 2 = rP1
R/W
2 byte
Process Data
0%
0xD0
0x00
Delay Switching Time 1
R/W
2 byte
0…500
0.1
sec
0
0xD1
0x00
Delay Back Switching Time 1
R/W
2 byte
0…500
0.1
sec
0
0xD2
0x00
Delay Switching Time 2
R/W
2 byte
0…500
0.1
sec
0
0xD3
0x00
Delay Back Switching Time 2
R/W
2 byte
0…500
0.1
sec
0
0xD5
0x00
Min Pressure Value
R
2 byte
Process Data
0xD6
0x00
Max Pressure Value
R
2 byte
Process Data
0xD7
0x00
Measure damping
R/W
2 byte
0…1000
in 10 ms steps
1
ms
0
Interfaccia IO-Link (continua)