SELECT
RUN
MODE
Set button 1 = On
indicator
indicator
indicator
indicator
Approx.
3 sec.
Make the object go through
during this period
H 325
Max. value
L 120
Min. value
Sensitivity setting (1)
The correct sensitivity setting can not be obtained if the sensors mutually
interfere with. Set sensitivity without cross talk of sensors.
Sensitivity setting in teaching mode -
Setting method differs as follows.
- Auto teaching: Set with an object still.
- Full auto teaching: Set with an object moving
Auto teaching (with an object still)
1) Confirm the switch is positioned on RUN
2) Push button 1 and then release it
without any objects.
The indicators flash to show standby
status.
3) Push button 1 with a detection object
placed on a proper position.
The flashing indicators stop flashing.
The setting is completed.
Addition
- In light variation indication mode, firstly teach a standard condition (±0) as an initially
taking data is set as a standard.
- When teaching starts to be carried out, LCD indication changes to show sensitivity and
level. After teaching is completed, the LCD indication will restored to be light variation
indication mode (+/-).
- When the switch is turned to SELECT or MODE under teaching, the teaching operation
stops with "non" indicated. The teaching resumes when the switch is turned to RUN again.
When teaching mode T, TV
is selected
Full auto teaching (with an object moving)
1) Confirm the switch is positioned on RUN
2) Hold to push button 1 for 3 sec.
or more. Orange LED and green
LED flash alternately and change
to be slow flashing.
3) Make the object go through while
the button continues to be pushed.
4) Release button 1 after the object
finished to go through and the LEDs
changed to be slow flashing.
When button 1 is released,
max. value and min. value
of the teaching are indicated.
(Max. and Min. are alternately
shown for 3 sec. )
The hold-to-teach feature is disabled under external teaching.
19