Photoelectric Sensors
Multi-function sensor with additional functions
BOS 21M-UUI-RP30-S4
6
english
Sensor function principle
The sensor supports four sensor function principles. The
IO-Link parameter
SensorPrinciple 0x00BB
can be used
to select between diffuse energetic sensor, diffuse sensor
with background suppression, retro-reflective and through-
beam (emitter or receiver).
The sensor is factory set to energetic diffuse. To implement
the through-beam function two units are required, with one
used as the emitter and the other as receiver.
Changing the sensor function principle takes
maximum 1500 ms.
Switch mode
In IO-Link mode the switching function can be configured
using the parameter 0x003D
SwitchpointConfiguration
.
The sensor can be operated using switching mode
Single
Point
,
Window
or
Two Point
. In
Single Point Mode
only the
first switchpoint SP1 is active. In
Window Mode
both
switchpoints SP1 and SP2 are active and form a window.
In
Two Point Mode
both switchpoints SP1 and SP2 are
active, where SP1 and SP2 form the hysteresis.
Single Point Mode
Two Point Mode
Window Mode
Deactivated
– N.O.: BDCx = 0
– N.C.: BDCx = 0
Fig. 6: Switch mode
Switch mode (continued)
Two static teach-in procedures (
Two Value Teach
and
Single Value Teach
) or a dynamic teach-in procedure
(Dynamic Teach)
can be used to teach the switchpoints
SP1 and SP2 in IO-Link mode.
Teach-In procedure
The current status of the teach-in procedure is indicated in
the parameter
Teach-In Status
.
Teach Flags
Teach State
SP2
SP1
TP2 TP1 TP2 TP1
Example:
0 = TP1 for SP1 not
taught or not successful
1 = TP1 for SP1
successfully taught
0 = IDLE
1 = SP1 SUCCESS
2 = SP2 SUCCESS
3 = SP12 SUCCESS
4 = WAIT FOR COMMAND
5 = BUSY
6 = reserved
7 = ERROR
Tab. 2: Teach-In Status
Teach-in is automatically canceled 10 min. after
start.
The teach-in sequences are explained using
SP1. The same sequence applies for SP2 using
the corresponding commands.
Prerequisite:
The sensor is mounted, aligned, and in IO-Link
operation.
Содержание BOS 21M-UUI-RP30-S4
Страница 1: ...deutsch Betriebsanleitung english User s guide français Notice d utilisation BOS 21M UUI RP30 S4 ...
Страница 2: ...www balluff com ...
Страница 3: ...BOS 21M UUI RP30 S4 Betriebsanleitung deutsch ...
Страница 25: ...BOS 21M UUI RP30 S4 User s guide english ...
Страница 47: ...BOS 21M UUI RP30 S4 Notice d utilisation français ...
Страница 69: ...www balluff com für Notizen to make notes pour vos notes personelles ...