Balluff / IO-Link BNI IOL-802-000-Z03x
www.balluff.com
20
4
IO-Link Interface
Mode
40
hex
The operating mode of the Smart Light can be selected in the Mode ISDU register.
0 = Segment mode
1 = Level mode
2 = Runlight mode
3 = Flexible mode*
*Available from software version 3.0
Number of
segments
41
hex
The number of the displayed segments can be set in this register. The minimum value for
the segment number is one and the maximum value is five.
Note
When the module is configured to have 3 segments, 1-1 LED is always switched of
between the segments.
Level type
42
hex
The type of the level indicator.
0 = bottom up
1 = top down
Level resolution
43
hex
The resolution of the input data in level mode.
0 = 8 bit
1 = 10 bit
2 = 12 bit
3 = 14 bit
4 = 16 bit
Level mode
segment x color
44
hex
45
hex
46
hex
47
hex
48
hex
Byte
0
Bit
7
6
5
4
3
2
1
0
D
es
cri
pt
ion
-
-
-
-
D
omi
na
nc
e
S
eg
men
t x
c
olor
S
eg
men
t x
c
olor
S
eg
men
t x
c
olor
Bit 0-2, Color of the segment
000 = Off
001 = Green
010 = Red
011 = Yellow
100 = Blue
101 = Orange*
110 = User defined*
111 = White
*color is available from software version 2.1
Bit 3, Color dominance
0 - Color is not dominant
1 - Color is dominant