Balluff Network Interface / IO-Link BNI IOL-719-002-Z012
www.balluff.com
8
3
Getting Started
3.5.
Sensor Interface
Standard I/O-port (M12, A-coded, female)
Pin
Voltage / Current input
1
+24 V, 150 mA (sensor supply)
2
Voltage / current input
3
GND (sensor supply, measurement)
4
Voltage / current input
5
-
Pin
Pt100, Pt1000 2 wire
1
Current Source 1 - / Analog In -
2
Current Source 1 - / Analog In -
3
Current Source 1 + / Analog In +
4
Current Source 1 + / Analog In +
5
-
Pin
Pt100, Pt1000 3 wire
1
Current Source -
2
Current Source 2 + / Analog In -
3
4
Current Source 1 + / Analog In +
5
-
Pin
Pt100, Pt1000 4 wire
1
Current Source -
2
Analog In -
3
Analog In +
4
Current
5
-
Pin
Thermocouple Typ J, Typ K, Typ C*
1
-
2
Thermo
3
Thermocouple -
4
-
5
-
* available from FW3.0
Note
The +24V supply voltage is short circuit protected. The supply voltage will be
switched off in case of short circuit, in order to reduce the power dissipation. The
short circuit error is latched and it can be reset with the output process data.
Note
In case of current input, the BNI IOL-719-002-Z012 works only with 3-wire
sensors.
2-wire-sensors are not supported with voltage or current input.
Содержание BNI IOL-719-002-Z012
Страница 1: ...BNI IOL 719 002 Z012 english User s Guide deutsch Betriebsanleitung...
Страница 2: ...www balluff com...
Страница 3: ...BNI IOL 719 002 Z012 Bedienungsanleitung...
Страница 37: ...BNI IOL 719 002 Z012 User s Guide...
Страница 71: ...BNI IOL 719 002 Z012...
Страница 104: ...IO Link BNI IOL 719 002 Z012 www balluff com 33...
Страница 105: ...www balluff com www balluff com 800 A 8 400 820 0016 400 920 2622 sales sh balluff com cn 932344_AB ZH G22 D22...