Balluff Network Interface / IO-Link
www.balluff.com
35
7
Configuration: BNI IOL-302-S02-Z012-C11 extended with 22/24 valve terminal
Safe state of
the outputs
42
hex
The safe state parameter makes it possible to configure the outputs in case of a fault. If no IO-
Link communication is possible or the "valid flag" of the output process data has not been set
by the master, then each output adopts the configured status.
The following states can be configured for each output pin.
Value
Output status (Safe State)
bin
dec
00
0
Output is 0 V
01
1
Output is 24 V
10
2
Current status is maintained
11
3
Not defined
Byte
0
1
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Sub-
index
4
3
2
1
8
7
6
5
S
af
e
st
at
e
of
…
P
o
rt
3
p
in
4
P
o
rt
2
p
in
4
P
o
rt
1
p
in
4
P
o
rt
0
p
in
4
-
P
o
rt
6
p
in
4
P
o
rt
5
p
in
4
P
o
rt
4
p
in
4
Byte
2
3
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Sub-
index
31
29
27
25
Valve terminal on the extension port
S
af
e
st
at
e
of
…
-
-
-
-
*
V
a
lv
e
1
2
–
C
o
il
A
V
a
lv
e
1
1
–
C
o
il
A
V
a
lv
e
1
0
–
C
o
il
A
V
a
lv
e
0
9
–
C
o
il
A
* No function with BNI IOL-751-V13-K007