background image

Balluff Network Interface / IO-Link  
 

 

www.balluff.com 

              

    

Safety 

  Intended Use 

  The BNI IOL-… acts as a decentralized input sensor module, which is connected to a 

higher-level IO-Link master module through an IO-Link interface. 

 

  Installation and 

Startup 

 

 

Attention! 

Installation and startup must only be carried out by trained technical personnel. 
Qualified personnel are people who are familiar with installation and operation of 
the product and have the necessary qualifications for these tasks. Any damage 
resulting from unauthorized tampering or improper use voids the manufacturer's 
guarantee and warranty. The operator must ensure that appropriate safety and 
accident prevention regulations are observed. 

 

 

  General Safety 

Instructions 

 

Commissioning and inspection 

Before commissioning, carefully read the user's guide. 
The system must not be used in applications in which the safety of persons is dependent 
upon proper functioning of the device. 

Authorized personnel 

Installation and startup must only be carried out by trained technical personnel. 

Intended use 

Warranty and liability claims against the manufacturer are rendered void by: 

 

Unauthorized tampering 

 

Improper use 

 

Use, installation or handling contrary to the instructions provided in this user's 
guide 

Obligations of the operating company 

The device is a piece of equipment in accordance with EMC Class A. This device can 
produce RF noise. The operator must take appropriate precautionary measures. The device 
may only be used with an approved power supply. Only use approved cables. 

Malfunctions 

In the event of defects and device malfunctions that cannot be rectified, the device must be 
taken out of operation and protected against unauthorized use. 
Intended use is ensured only when the housing is fully installed. 

 

  Resistance to 

aggressive 
substances 

 

 

Attention!  

The BNI modules generally have a good chemical and oil resistance. When 
used in aggressive media (eg chemicals, oils, lubricants and coolants each in 
high concentration (ie, low water content)) must be checked prior application-
related material compatibility. In the event of failure or damage to the BNI 
modules due to such aggressive media are no claims for defects. 

 

 

Hazardous 
voltage 

 

 

Attention! 

Before maintenance, disconnect the device from the power supply. 

 

 

 

 

 

Note 

In the interests of product improvement, Balluff GmbH reserves the right to 
change the technical data of the product and the content of this manual at any 
time without notice. 

 

 
 

Содержание BNI IOL-104-S02-Z012

Страница 1: ...BNI IOL 104 S02 Z012 IO Link 1 1 Sensor Hub with extension port User s Guide...

Страница 2: ...nfiguration of the Extension Port 11 Data handling with the Extension Port 12 5 Configuration BNI IOL 104 S02 Z012 extension port off 13 Extension Port Configuration 13 IO Link Data 13 Process Data In...

Страница 3: ...utputs 42hex 25 Voltage monitoring 44hex 27 Output monitoring 45hex 28 Setting the serial number 54hex 28 Configuration of the extension port 55hex 28 8 Error Codes and Events 29 Error Codes Errors 29...

Страница 4: ...tructions are indicated by a preceding triangle The result of an action is indicated by an arrow Action instruction 1 Action result Action instruction 2 Syntax Numbers Decimal numbers are shown withou...

Страница 5: ...oid by Unauthorized tampering Improper use Use installation or handling contrary to the instructions provided in this user s guide Obligations of the operating company The device is a piece of equipme...

Страница 6: ...overview Figure 3 1 Connection overview 1 Mounting hole 2 Label 3 Communication state 4 Port 1 5 Port 3 6 Port 5 7 Port 7 Extension Port 8 Pin Port LED Signal status 9 Port 6 10 Port 4 11 Port 2 12 Po...

Страница 7: ...kept as short as possible IO Link connection The IO Link connection is established via an M12 connector A coded male This connector is used for powering the module In some devices this connector is al...

Страница 8: ...Requirement 1 24V 200mA 2 PNP Input 2 3 0V GND 4 PNP Input 1 5 FE Note For the digital inputs the input guideline specified in EN 61131 2 Type 3 applies Note Unused input port sockets must be fitted w...

Страница 9: ...e modules provide using the Port 7 in various ways By default it is used as a digital input port where both pin 2 and pin 4 can be used as a digital input Additionally this port can be used as an Exte...

Страница 10: ...Process Data In Configuration of Extension Port Process Data Input Bytes 0 1 2 3 4 5 6 7 0 BNI IOL 104 S02 Z012 Input State Diagnostic Info 1 BNI IOL 104 S02 Z012 same device Input State Diagnostic I...

Страница 11: ...K007 The device which is connected to the Extension Port is called as Second Device in this manual Note The Factory reset command does not affect the configuration of the extension port in any way Not...

Страница 12: ...ort When the Extension Port is activated the content and length of the Process Data or ISDU is calculated as the union of the process data or ISDU provided by the two parties PD result PD of first dev...

Страница 13: ...ration is Extension Port off Configuration ISDU Index 55hex value Device alone Extension Port not active 0 Device with same device 1 Device with BNI IOL 751 V08 K007 2 Device with BNI IOL 751 V10 K007...

Страница 14: ...t 7 Pin 4 Port 6 Pin 4 Port 5 Pin 4 Port 4 Pin 4 Port 3 Pin 4 Port 2 Pin 4 Port 1 Pin 4 Port 0 Pin 4 Port 7 Pin 2 Port 6 Pin 2 Port 5 Pin 2 Port 4 Pin 2 Port 3 Pin 2 Port 2 Pin 2 Port 1 Pin 2 Port 0 P...

Страница 15: ...ame BNI IOL 104 S02 Z012 13hex 19 0 Product ID 7 bytes BNI00CR 14hex 20 0 Product text Sensor Hub M12 15hex 21 0 Serial number 16 bytes various 16hex 22 0 Hardware Revision 17hex 23 0 Firmware Revisio...

Страница 16: ...SC Port 6 Pin 1 SC Port 5 Pin 1 SC Port 4 Pin 1 SC Port 3 Pin 1 SC Port 2 Pin 1 SC Port 1 Pin 1 SC Port 0 Pin 1 Undervoltage US1 Setting the serial number 54hex The serial number has a factory default...

Страница 17: ...n Configuration ISDU Index 55hex value Device alone Extension Port not active 0 Device with same device 1 Device with BNI IOL 751 V08 K007 2 Device with BNI IOL 751 V10 K007 3 Device with BNI IOL 751...

Страница 18: ...4 3 2 1 0 Voltage monitoring SC Port 7 Pin 1 SC Port 6 Pin 1 SC Port 5 Pin 1 SC Port 4 Pin 1 SC Port 3 Pin 1 SC Port 2 Pin 1 SC Port 1 Pin 1 SC Port 0 Pin 1 Undervoltage US1 Byte 4 5 Bit 7 6 5 4 3 2...

Страница 19: ...12 with BNI IOL 104 S02 Z012 13hex 19 0 Product ID BNI00CR with BNI00CR 14hex 20 0 Product text Sensor Hub M12 extended with Sensor Hub M12 15hex 21 0 Serial number 16 bytes various 16hex 22 0 Hardwar...

Страница 20: ...2 Pin 4 Port 1 Pin 4 Port 0 Pin 4 Port 6 Pin 2 Port 5 Pin 2 Port 4 Pin 2 Port 3 Pin 2 Port 2 Pin 2 Port 1 Pin 2 Port 0 Pin 2 Byte 2 3 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Sub index 24 23 22 21 20 19 18...

Страница 21: ...sion Port Voltage monitoring SC Port 7 Pin 1 SC Port 6 Pin 1 SC Port 5 Pin 1 SC Port 4 Pin 1 SC Port 3 Pin 1 SC Port 2 Pin 1 SC Port 1 Pin 1 SC Port 0 Pin 1 Undervoltage US1 Setting the serial number...

Страница 22: ...not active 0 Device with same device 1 Device with BNI IOL 751 V08 K007 2 Device with BNI IOL 751 V10 K007 3 Device with BNI IOL 751 V13 K007 4 However BNI IOL 104 S02 Z012 is a digital input module...

Страница 23: ...Pin 1 SC Port 5 Pin 1 SC Port 4 Pin 1 SC Port 3 Pin 1 SC Port 2 Pin 1 SC Port 1 Pin 1 SC Port 0 Pin 1 Outputs off UA too low Undervoltage UA Undervoltage US1 Process Data Output Data No function for B...

Страница 24: ...BNI00CR with BNI006P BNI00CR with BNI006R 14hex 20 0 Product text Sensor Hub M12 extended with Valve Plug CG25 24 2 3 Sensor Hub M12 extended with Valve Plug CG13 24 2 3 Sensor Hub M12 extended with V...

Страница 25: ...erted Safe state of the outputs 42hex The safe state parameter makes it possible to configure the outputs in case of a fault If no IO Link communication is possible or the valid flag of the output pro...

Страница 26: ...A Valve 01 Coil A Byte 4 5 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Sub index 24 22 20 18 Valve terminal on extension port Safe State of Valve 12 Coil B Valve 11 Coil B Valve 10 Coil B Valve 09 Coil B No...

Страница 27: ...Sub index 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9 Voltage monitoring SC Port 7 Pin 1 SC Port 6 Pin 1 SC Port 5 Pin 1 SC Port 4 Pin 1 SC Port 3 Pin 1 SC Port 2 Pin 1 SC Port 1 Pin 1 SC Port 0 Pin 1 Out...

Страница 28: ...2 Valve terminal on extension port Short circuit of Valve 12 Coil B Valve 11 Coil B Valve 10 Coil B Valve 09 Coil B Valve 08 Coil B Valve 07 Coil B Valve 06 Coil B Valve 05 Coil B Valve 04 Coil B Val...

Страница 29: ...available Events IO Link Revision 1 0 Event code Description 0x5112 Low sensor voltage US 0x5114 Low actuator voltage UA 0x5410 Output stages 0x8DF0 Retry at the extension port 0x8DF1 Device lost at t...

Страница 30: ...stored configuration is automatically transferred to the new device This guarantees minimal downtime Validation must be switched on in order to use the data storage For information about the configur...

Страница 31: ...sions H x W x D without connector 68 x 181 5 x 31 8 mm Electrical Data Supply voltage 18 30 2 V DC corresponding to EN 61131 2 Supply power on M12 connector 4 A Ripple 1 Current consumption without lo...

Страница 32: ...puts Indicator Description LED 0 Input on Pin4 LED 1 Input on Pin2 Status Function Yellow Input signal 1 Red Sensor power supply short circuit Off Input signal 0 Extension port The table is valid if t...

Страница 33: ...S02 Z012 BNI00CR BNI IOL xxx xxx Zxxx Balluff Network Interface IO Link interface Functions 104 16 PNP inputs Variants S02 with IO Link 1 1 extension port and single channel monitoring Mechanical conf...

Страница 34: ...www balluff com www balluff com Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a d F Germany Tel 49 7158 173 0 Fax 49 7158 5010 balluff balluff de No 940290 E Edition E18 Subject to modification...

Отзывы: