www.balluff.com
9
english
4.2
Function
The IO-Link hubs have eight input ports with a total of 16
inputs. The connection to the higher-level master module is
made via the IO-Link protocol.
In terms of function, the hub module is comparable to a
passive distribution box: Pick up digital signals and forward
them via the IO-Link interface.
4.3
Display elements
Fig. 4-3:
LED 1
LED 0
IOL
U
S
Display elements
Module status LEDs
LED Display
Meaning
U
S
Green, static Voltage in the nominal range
Green, fast
flashing
Operating voltage of the device is
too low (< 18 V).
Off
Module without supply voltage
IOL
Green,
negative
pulsing
IO-Link communication is active.
The device is ready.
Green, static No communication
Off
Module without supply voltage
Tab. 4-1: Status LEDs
4
Product description (continued)
LEDs of the digital inputs (LED 0, input Pin 4 and
LED 1, input Pin 2)
Display
Meaning
Yellow, static Input signal = 1
Red, static
Sensor supply short circuit
Off
Input signal = 0
Tab. 4-2: LEDs of digital inputs
4.4
Labeling
Front
Fig. 4-4:
Type
Printing on front
Side
1)
2)
3)
4)
1
Hardware version
2)
Software version
3)
Order code
4)
Manufacturing date and country code
Fig. 4-5: Side printing (example)
BNI IOL-104-011-K006
Network interface – Digital hub
Содержание BNI IOL-104-011-K006
Страница 1: ...BNI IOL 104 011 K006 deutsch Betriebsanleitung english User s Guide...
Страница 2: ...www balluff com...
Страница 3: ...BNI IOL 104 011 K006 Betriebsanleitung deutsch...
Страница 4: ...www balluff com...
Страница 21: ...BNI IOL 104 011 K006 User s Guide english...
Страница 22: ...www balluff com...
Страница 39: ......