Sensor connection:
Only connect to intrinsically safe certified circuits or evalua-
tion amplifiers which do not exceed the following maximum values of the units:
• Maximum effective internal inductance (Li) and capacitance (Ci) per sensor:
Notes on installation/mounting
• Always observe the applicable national regulations and legal provisions.
• Always observe the applicable installation regulations.
• Avoid electrostatic charging on plastic units and cables.
• If used in zone 0, the sockets must be protected against strong electros-
tatic charging.
• To avoid electrostatic charging ensure that metal parts (plug housing,
fittings, etc.) are equipotentially grounded.
• Ensure that the units are efficiently protected against damage.
• The units must not be installed in the partitions between different zones.
Special conditions to ensure safe operation
• Always refer to the operating instructions as space restrictions may not
allow all markings to be applied to the unit.
Maintenance/repair
The unit must not be modified in any way and can not be repaired. In the
event of a fault please contact the manufacturer.
If required, data sheets, the EC Declaration of Conformity or type test
certificates may be obtained from the manufacturer (see cover sheet).
5
IRL
GB
ENGLISH
U
i
= 15 V,
I
i
= 50 mA, P
i
= 120 mW
Model No.
115
210
BES M12ME-GNX40B-S04G-EEX
Internal inductance
in μH
Internal capacitance
in nF
190
200
BES M18ME1-GNX80B-S04G-EEX
210
230
BES M30ME1-GNX15B-S04G-EEX
BES Q40KFU-GNX20B-S92G-EEX
450
250
710
220
BES Q40KFU-GNX35F-S92G-EEX