Capacitive Proximity Switches BCS R08RRE…
www.balluff.com
15
Index
Name
Data type
Sub-
index
Access
Data range
Description
0x0028
(40)
Process Data
Input
UINT16
R
Actual Process Data
0x003A
(58)
Teach-In
Channel
UINT8
R/W
0
–
All BDCs
0x003B
(59)
Teach-In Status
UINT8
R
State of the Teach State
Machine
- State
UINT4
- Bit 0
0 - Idle
1
–
SP1 Success
7 - Error
- Flag SP1.TP1
- Bit 4
FALSE, TRUE =
Teach successfull
Teachpoint SP1.TP1
- Flag SP1.TP2
- Bit 5
FALSE, TRUE =
Teach successfull
Teachpoint SP1.TP2
- Flag SP2.TP1
- Bit 6
FALSE
Teachpoint SP2.TP1
- Flag SP2.TP2
- Bit 7
FALSE
Teachpoint SP2.TP2
0x003C
(60)
Setpoints BDC1
Array
- SP1
UINT16
1
R/W
0
…
4095
Switchpoint SP1
- SP2
UINT16
2
R/W
0
…
4095
Switchpoint SP2 is not used
and is always read as 0
0x003D
(61)
Switch Point
Mode
Array
- Logic
UINT8
1
R/W
0
–
Normally Open,
1
–
Normally Closed
default = 0
Switching function
- Mode
UINT8
2
R
1
–
Single Point
Mode
Operating mode switchpoint
- Hysteresis
UINT8
3
R/W
0 to 10, default = 5
Hysteresis switchpoint
0x00B2
(178)
Delay
Array
- On
UINT8
1
R/W
Standard: 0 to 1280
SmartLEVEL: 0 to
2560
default = 0
Delay ON (in ms)
- Off
UINT8
2
R/W
See
Delay.On
Delay OFF (in ms)
- Filter
UINT8
3
R/W
See
Delay.On
Filter time (in ms)
0x00B4
(180)
SIO Output
Mode
UINT8
R/W
1
–
PNP, default
2
–
NPN
3
–
PushPull
Switching output type
Switching function is indicated
in Switch Point Mode.Logic
System commands
Value
Name
Description
0x4D (77)
Teach Full
Full calibration
0x4E (78)
Teach Empty
Empty calibration