www.balluff.com
19
Mode Start/Stop
This menu defines the operating as Start / Stop – interface converter.
INIT MODE
Operating mode: Master or Slave
Depending on the selected INIT MODE, different terminals must be used for the Init pulse!
(Mode Master: terminal X2 – Pin 1 and 2 / Mode Slave: terminal X2 – Pin 5 and 6)
0
MASTER
Master-operation: Init pulse is generated by the device.
1
SLAVE
Slave-operation: Init pulse comes from an external master.
SAMPLING TIME (ms)
Period duration between two init pulses (in milliseconds). Corresponds to the time after a new
measurement is started and directly affects the reaction time of the device.
00.200
Minimum measurement time
04.000
Default value
16.000
Maximum measurement time
INIT PULSE TIME (µs)
This parameter defines the pulse width of the Init pulse (in microseconds).
1
Smallest value
2
Default value
9
Highest value
VELOCITY (m/s)
Waveguide velocity of the encoder (in m/s).
0001.00
Smallest value
2800.00
Default value
9999.99
Highest value
OPERATIONAL MODE
This parameter determines which measurement type the device should run.
0
POSITION
Distance measurement
1
ANGLE
Angle measurement
2
SPEED
Speed measurement
Note: For further information regarding the different "OPERATIONAL MODES"
and interpretation of the respective measurement results see appendix!
OFFSET
In the case of a “Reset/Set Value” command (via control input or PC user interface) the current
position of the encoder is transferred to the “OFFSET” parameter in a non-volatile manner. (zero
offset!)
-99999999
Smallest value
0
Default value
99999999
Highest value