www.balluff.com
33
Analog Menu
This menu defines the basic settings of the analog output. The analog output always
refers to the scaled "Measurement Result"!
ANALOG FORMAT
This parameter defines the output characteristics. The analogue output is proportional to the
display value.
With setting ANALOG FORMAT (-
10 … +10 V) in MODE COUNTER the p
olarity of the analog
output depends on the polarity of the display value.
0
-
10…10V
-
10 … +10 V
1
0…20MA
0 … 20 mA
2
4…20MA
4 … 20 mA
ANALOG START
This parameter defines the start value of the analog conversion. This start value is corresponding
to the display value for an analog output of 0 V or 0/4 mA.
-99999999
Smallest end value
0
Default Wert
+99999999
Highest end value
ANALOG END
This parameter defines the end value of the analog conversion. This end value is corresponding
to the display value for an analog output of (+/-) 10 V or 20 mA.
-99999999
Smallest end value
10000
Default Wert
+99999999
Highest end value
ANALOG GAIN (%)
This parameter specifies the maximum conversion of the analog output in %.
e. g. 102.00 corresponds to a conversion of 10.2 V or 20.4 mA, when the ANALOG END value is
reached.
e. g. 95.00 corresponds to a conversion of 9.5 V or 18 mA, when the ANALOG END value is
reached.
0,00
Smallest gain
100,00
Default value
110,00
Highest gain
ANALOG OFFSET (%)
This parameter defines the zero offset of the analog output.
z. B. 0.20 result in an offset of 0.02 V or 0.04 mA at ANALOG START value
-99,99
Smallest offset
0
Default value
+99,00
Highest offset