Control Inputs (X5)
At terminal X5 pins 2,3,4,5,6 and 7 there are six control inputs with HTL PNP
characteristic available.
Control Input 1 (Ctrl. In 1) to Control Input 5 (Ctrl. In 5) are freely configurable in the
COMMAND MENU and are used for functions to be triggered externally. eg. for releasing
the latching, resetting the measurement result or for teaching the preset values or the
analog output.
Control input 6 (Ctrl. In 6) is used exclusively for resetting the device parameters to the
"default" values. Thus, it is not freely configurable.
Note: With an HTL pulse (rising edge) on Ctrl. In 6, the device is reset to
the factory settings.
Wiring of the
control inputs
:
Unconnected control inputs are always “LOW”.
All inputs are designed to receive impulses from an electronic impulse source.
Notice for mechanical switching contacts:
When exceptionally mechanical contacts are used, please connect an external capacitor
between GND (-) and the corresponding input (+). A capacity of 10 µF will reduce the
input frequency to 20 Hz and miscounting due to contact bouncing will be eliminated.