2

English

Lifetime indicators (service life)

 

The LEDs indicate the remaining service life of the device. 
It is based on the sum of all loads. The service life starts at 
15 years and decreases depending on the stress level and 
the load. 

Load level indicator (load level)

 

The LEDs indicate the current load of the device without 
any delay: 

Display elements

Stress level indicator (Voltage level)

 

The green, yellow and red LEDs indicate the electrical and 
thermal load. This data is collected and evaluated during a 
three-hour cycle. The operator is thereby able to check 
and then modify the ambient conditions to prevent nega-
tive influences on the device.

 

Installation (continued)

Internal fuse

The internal input fuse protects the device and cannot be 
replaced. If an internal fault occurs, return the device to the 
manufacturer as a precautionary measure. 

Rail mounting

Provide sufficient ventilation and cooling. Do not obstruct 
the ventilation holes. 

 

Slightly tip the device to the rear.

 

Affix the device to the upper edge of the rail.

 

Slide down until it stops.

 

To latch, press on the lower front side.

 

Shake the device gently to verify that it has been 

latched. 

Removal

 

Switch off the power supply and disconnect the sys-

tem from mains. Disconnect all connectors from the 

power supply.

 

Slide the latch guard down (unlatch).

 

Slightly raise the front edge of the device (tip) and 

remove.

Symbol

Meaning

Green

Low pulse speed: everything OK, a long 

service life can be expected.

Yellow

Pulse speed increasing: thermal load not 

optimum. No immediate risk of overheating. 

Slightly accelerated aging. Reduce the load 

or improve ventilation!

Red

High pulse speed: poor internal 

thermal state, service life at serious risk. 

Check the load and improve ventilation!

Symbol

Meaning

Green

Power supply with long service life

Yellow

Service life less than 3 years, replace during 

next maintenance cycle

Red

Power supply at end of service life, replace 

immediately

Symbol

Meaning

Green

0...80% load

Yellow

81...100% load

Red

>100...150% load, typically when a higher 

current is required, max. 4 s

Indicator elements (continued)

Error indicator

As soon as the output voltage lies outside of 
the working range 22...28 V DC (e.g., short 
circuit), only the load level indicator illuminates 
red. The other two indicators are switched off.

Operating elements

Potentiometer

Used for setting the output voltage.

Switching power supplies IO-Link ready

MAN-SHG BAE PS-XA-1S-24-200-104

Содержание BAE PS-XA-1S-24-200-104

Страница 1: ...as Ger t nicht abdecken F r die K hlung ausreichenden Raum um das Ger t herum vorsehen sonst kann das Ger t durch berhi tzung abgeschaltet werden Die Lebensdauer des Ger ts sinkt sobald es l nger im b...

Страница 2: ...Lebensdauer beginnt bei 15 Jahren und nimmt ent sprechend des Stressniveaus und der Belastung ab Load Level Anzeige Belastungsniveau Die LEDs signalisieren verz gerungsfrei die aktuelle Auslas tung de...

Страница 3: ...rm Der Kontakt schlie t sobald die Ausgangsspannung au erhalb von 21 V 28 5 V DC liegt z B wenn ein Kurzschluss ansteht Kontakt Stresslevel Der Kontakt schlie t sobald die Stresslevel LED auf rot scha...

Страница 4: ...ailable 0x8012 Subindex not available 0x8023 Access Denied 0x8030 Parameter Value out of Range 0x8033 Paremeter length overrun 0x8034 Parameter length underrun 0x8035 Function not available IO Link In...

Страница 5: ...t 1 R W 2 Process Data Over load 0 1 A 0x3D 0x03 BDC1 Hysteresis R W 2 0 0xFFFF 0 1 A 0x3E 0x01 BDC2 SetPoint 1 R W 2 Process Data Over voltage 0 1 V 0x3F 0x03 BDC2 Hysteresis R W 2 0 0xFFFF 0 1 V 0x5...

Страница 6: ...auigkeit 1 0 Spannungsregelung 0 5 Lastregelung 0 5 Lasttyp resistive capacitive Technische Daten Werte gemessen bei 25 C und Volllast Mechanische Daten Werkstoff Geh use Metall Gewicht 1 1 kg Abmessu...

Страница 7: ...he device Ensure that there is sufficient space around the device to allow for cooling otherwise the device may shut down due to overheating The service life of the device is shortened once it is oper...

Страница 8: ...e gently to verify that it has been latched Removal Switch off the power supply and disconnect the sys tem from mains Disconnect all connectors from the power supply Slide the latch guard down unlatch...

Страница 9: ...ntact closes as soon as the output voltage lies between 21 V and 28 5 V DC e g when there is a short circuit Stresslevel contact The contact closes as soon as the Stresslevel LED turns red Connections...

Страница 10: ...vailable 0x8012 Subindex not available 0x8023 Access Denied 0x8030 Parameter Value out of Range 0x8033 Paremeter length overrun 0x8034 Parameter length underrun 0x8035 Function not available IO Link I...

Страница 11: ...1 BDC1 SetPoint 1 R W 2 Process Data Over load 0 1 A 0x3D 0x03 BDC1 Hysteresis R W 2 0 0xFFFF 0 1 A 0x3E 0x01 BDC2 SetPoint 1 R W 2 Process Data Over voltage 0 1 V 0x3F 0x03 BDC2 Hysteresis R W 2 0 0x...

Страница 12: ...0 5 Load type resistive capacitive Technical data Values measured at 25 C and full load Mechanical data Housing material Metal Weight 1 1 kg Dimensions W x H x D mm 73 5 x 127 x 137 Terminal 0 25 mm 4...

Страница 13: ...Ne pas couvrir le dispositif Afin d assurer le refroidissement d un espace suffisant pour l appareil celui ci peut galement tre arr t via une surchauffe La dur e de vie du dispositif diminue d s lors...

Страница 14: ...il D montage D sactiver l alimentation lectrique et d brancher le syst me du r seau d alimentation D brancher l ensemble des connecteurs du bloc d alimentation Pousser la protection de verrouillage ve...

Страница 15: ...sortie se trouve en dehors de 21 V 28 5 V DC p ex en cas de court cir cuit Contact Stresslevel niveau de charge Le contact se ferme d s que la LED Stresslevel commute en rouge Connexions Fig 2 Connex...

Страница 16: ...Error Codes Error Code Description 0x8011 Index not available 0x8012 Subindex not available 0x8023 Access Denied 0x8030 Parameter Value out of Range 0x8033 Paremeter length overrun 0x8034 Parameter le...

Страница 17: ...R 1 0 4 0x3C 0x01 BDC1 SetPoint 1 R W 2 Process Data Over load 0 1 A 0x3D 0x03 BDC1 Hysteresis R W 2 0 0xFFFF 0 1 A 0x3E 0x01 BDC2 SetPoint 1 R W 2 Process Data Over voltage 0 1 V 0x3F 0x03 BDC2 Hyste...

Страница 18: ...Courant de sortie nominal 20 A Puissance de sortie 480 W Plage de r glage 22 28 V DC Pr cision de la tension de sortie 1 0 R gulation de tension 0 5 R gulation de charge 0 5 Type de charge resistive c...

Страница 19: ...er consentire il raffreddamento dell apparecchio assicurarsi che esso abbia spazio sufficiente intorno a s in caso contrario il surriscaldamento potr cau sarne lo spegnimento La durata dell apparec ch...

Страница 20: ...arecchio Smontaggio Staccare la corrente e separare il sistema dalla rete di alimentazione Separare tutti i connettori dall alimentatore Spingere verso il basso la protezione del bloccaggio sbloccare...

Страница 21: ...Alarm Il contatto chiude non appena la tensione in uscita oltre 21 V 28 5 V CC ad es in presenza di cortocircuito Contatto Stresslevel Il contatto chiude non appena il LED Stresslevel commuta su luce...

Страница 22: ...4 4 Error High stress level 0xB005 0x1805 4 Warning Fast aging 0xB006 0x1806 4 Warning Over Tempera ture 0xB007 0x1807 4 Warning Over load 0xB008 0x1808 4 Warning Informazioni generali sull apparecchi...

Страница 23: ...3C 0x01 BDC1 SetPoint 1 R W 2 Process Data Over load 0 1 A 0x3D 0x03 BDC1 Hysteresis R W 2 0 0xFFFF 0 1 A 0x3E 0x01 BDC2 SetPoint 1 R W 2 Process Data Over voltage 0 1 V 0x3F 0x03 BDC2 Hysteresis R W...

Страница 24: ...Campo di regolazione 22 28 V DC Precisione di uscita 1 0 Regolazione di tensione 0 5 Regolazione del carico 0 5 Tipo di carico resistive capacitive Dati meccanici Materiale della custodia Metal Peso 1...

Страница 25: ...cio alrededor del aparato para la refrigeraci n para evitar que el aparato pueda desconectarse debido a un calentamiento excesivo La vida til del aparato se reduce si funciona durante un tiempo prolon...

Страница 26: ...riente y separar el sistema de la red de alimentaci n Separar todos los conectores de la fuente de alimentaci n Empujar hacia abajo la protecci n de bloqueo des bloquear Elevar ligeramente el borde fr...

Страница 27: ...nto la tensi n de salida se encuentra fuera de 21 V 28 5 V CC p ej cuando se produce un cortocircuito Contacto nivel de estr s El contacto se cierra en cuanto el nivel de estr s del LED conmuta a rojo...

Страница 28: ...es Definition Event Codes IO Link 1 1 Event Codes IO Link 1 0 Device status Type No malfunction 0x0000 0x0000 0 Notifica tion General mal function Unknown error 0x1000 0x1000 4 Error Process variable...

Страница 29: ...0x3C 0x01 BDC1 SetPoint 1 R W 2 Process Data Over load 0 1 A 0x3D 0x03 BDC1 Hysteresis R W 2 0 0xFFFF 0 1 A 0x3E 0x01 BDC2 SetPoint 1 R W 2 Process Data Over voltage 0 1 V 0x3F 0x03 BDC2 Hysteresis R...

Страница 30: ...ajuste 22 28 V DC Precisi n de salida 1 0 Regulaci n de tensi n 0 5 Regulaci n de carga 0 5 Tipo de carga resistive capacitive Datos mec nicos Material de la carcasa Metal Peso 1 1 kg Dimensiones B x...

Отзывы: