    Air Conditioner Service Manual 

 

6

3, Dry mode

   

running into this mode, the Air cond. firstly operates for 3 minutes according to cooling mode (set 
temperature is 7

) , and then takes the detected backflow air temperature minus 2

 as a new set 

temperature (the minimum value of 5

) and runs according to cooling mode, indoor fan operates at 

low-speed, at this moment the setting operation of Fan speed is invalid but Swing is adjustable. 
4. Heating mode 
   On the Heating mode, the room temperature is repaired. After repaired, the room temperature 
display on the LED CRT=RT-3

1) The control of the compressor 
a. When ST

CRT

1

the compressor is running. 

b. When ST

CRT

-1

the compressor is off. 

c. When -1

ST

CRT

1

, the compressor keeps its original state 

2) Outdoor fan motor and the compressor run simultaneously (except for defrosting) 
3) The control of indoor fan motor: 
a. Indoor fan motor can operate by automatic, low, middle, and high airflow speed circularly. 
b. indoor fan motor’s the automatic airflow speed control Indoor fan motor can operate by automatic

as shown in Figure 2: 
 

                Hi   
                Mid   

 Lo  

                ST

CRT                                                            1

          2

                  4

 

Figure 2 Heating automatic airflow 

When the temperature changes lead to changes in airflow speed, the switch can only be made 
orderly, and every grade of air flow speed runs 1 minute at least. 
4) Vane motor control: run as set state. 
5) 4-way valve control: 
a. Under heating mode, the four-way valve maintains well-connected status (including the 
compressor stops on set condition, but except for the defrosting process) 
b. When the mode switches into the heating mode or start-up, four-way valves will open 5 Seconds 
before the compressor starts; while the mode exits from the heating mode or turn off, the four-way 
valve will close 2min after after the shut-down the compressor. 
6) Defrosting function: 
During defrosting, once mode switch, temperature setting signals received, and the buzzer and 
display make response immediately, but the other operations won’t implemented until defrosting 
finished; 
During defrosting, the signals of on-off, timing, sleep, airflow speed ans swing will be responded, but 
the airflow speed and swing should be in accordance with anti-cold air rules. 
Except the above signal processing during defrosting, no other signals will be dealt with, but only a 
loud buzz.   
During defrosting, electrical heating stops compulsively. 
Defrosting enter and exit pragram: 
Option 1

with jumper JC 

The condition of enter defrosting: run into defrosting once any of condition 1, 2, and 3 met. 

Содержание BSZ-30H

Страница 1: ...TED SPLIT TYPE AIR CONDITIONERS CONTENTS 1 IMPORTANT NOTICE 2 2 TECHNICAL SPECIFICATION 3 3 OPERATION DETAILS 4 4 WIRING DIAGRAM 12 5 EXPLOSION VIEW 13 6 PARTS LIST 15 Models BSZ 30H SERVICE MANUAL No...

Страница 2: ...information nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modification or improvement without any prior...

Страница 3: ...type 9 52 Expansion device Capillary tube Defrosting system Microcomputor controlled reverse system Fan System Indoor air circulation Hi Cooling m3 h 1200 1200 Indoor fan type Cross flow Cooling rpm 1...

Страница 4: ...oller 6 2 5 3 7 1 1 1 Air Conditioner Service Manual Operation Details Remote Control The remote controller is not presetted as Cooling Only Air Conditioner or Heat Pump by manufacturer Each time afte...

Страница 5: ...e Initial RT Initial ST Cooling RT 26 23 Dehumifying 26 RT 20 18 Heating RT 20 23 Cooling only Mode Initial RT Initial ST Cooling RT 26 23 Dehumifying 26 RT 20 18 Ventilating RT 20 Under automatic mod...

Страница 6: ...ature changes lead to changes in airflow speed the switch can only be made orderly and every grade of air flow speed runs 1 minute at least 4 Vane motor control run as set state 5 4 way valve control...

Страница 7: ...g temperature droping when compressor operating not including the compressor s starting course and the machine runs into defrosting according to any one condiciton as below Running into defrosting und...

Страница 8: ...e quitting conditions for option 3 When OPT 20 C or defrosting for more than 10 min then quit from defrosting 3 Defrosting process shown in Figure 4 Figure 4 Defrosting process 7 Auxiliary Electric he...

Страница 9: ...buzzer rings once and to release the machine runs into cooling mode if to holding on the buzzer rings twince then the machine runs into heating mode while when the machine is on to press the emergency...

Страница 10: ...or and the compressor open indoor fan motor restores the original state 4 Anti cold wind control in heating a When runing into the heating mode once the compressor fails to comply with the start up co...

Страница 11: ...sor failures appear the compressor stops and indoor and outdoor fan motors shut off Remote controller deesn t response to any signal except for shutdown During failure the machine can run in fan mode...

Страница 12: ...Air Conditioner Service Manual 12 WIRING DIAGRAM MODEL BSZ 30H INDOOR UNIT OUTDOOR UNIT...

Страница 13: ...Air Conditioner Service Manual 13 EXPLOSION VIEW MODEL BSZ 30H INDOOR UNIT 8 13 11 12 10 9 6 7 5 4 3 1 2 17 14 15 16 18 20 1 26 25 23 21 22 24 27...

Страница 14: ...Air Conditioner Service Manual 14 EXPLOSION VIEW MODEL BSZ 30H OUTDOOR UNIT 10 11 8 9 6 7 5 4 20 14 12 13 15 16 17 18 19 3 2 21 22 24 23 25 26 1 27 29 28...

Страница 15: ...B Cover 1 14 1070850180 Up Vane 1 15 1070850181 Down Vane 1 16 1070110012 Drainage Hose 1 17 1070850140 Cable Clamp 1 18 1170020023 Vane Motor 2 19 1170200051 Terminal 1 20 1073030201 Sensor Holder 1...

Страница 16: ...1081990039 Right Plate 1 16 1120120011 Two way Valve 1 17 1081990041 Valve Supporter 1 18 1120130013 Three way Valve 1 19 1073551103 Electrical Box Cover 1 20 1074060118 Cable Clamp 1 21 1170200054 T...

Отзывы: